TP-6200 10/12 91Section 2 Operation
Local Programming Mode On
Menu 7—Generator System, continued
Menu 7 Displays with Key Entries
Key
Entry Display Description
Displays the phase configuration selection. Note: The display
sample may differ depending upon previous entries. The
user-selected phase appears first, either wye, delta, or single phase.
PHASE →
3 PHASE DELTA NO
Displays the optional phase configuration selection. When required,
use the YES key to choose the delta phase configuration.
PHASE →
(see note) YES
KW RATING ?
Displays the generator set kW rating as entered data. When
required, use the numeric keys to set the new value. Press the Enter
key.
PHASE →
3 PHASE DELTA YES
Enter YES to change the phase configuration to a delta phase
configuration and press the Enter key.
PHASE →
3 PHASE DELTA YES
Confirms the entry. See NOTE A.
OR
PHASE →
3 PHASE WYE NO
Displays the optional phase configuration selection. When required,
use the YES key t o choose the wye phase configuration.
PHASE →
3 PHASE WYE YES
Enter YES to change the phase configuration to a wye phase
configuration and press the Enter key.
PHASE →
3 PHASE WYE YES
Confirms the entry. See NOTE A.
OR
PHASE →
SINGLE-PHASE NO
Displays the optional phase configuration selection. When required,
use the YES key t o choose the single-phase configuration.
PHASE →
SINGLE-PHASE YES
Enter YES to change the phase configuration to a single-phase
configuration and press the Enter key.
PHASE →
SINGLE-PHASE YES
Confirms the entry. See NOTE A.
KW RATING #
Displays the corrected system kilowatt rating.
LOAD SHED OUTPUT →
?% # KW
Displays the load shed output setting. When required, use the
numeric keys to set the new value. Press the Enter key. See Menu
10, Output Setup for Group B User-Defined Systems Events
Displays the corrected load shed output setting.
LOAD SHED OUTPUT →
#% # KW
TIME DELAY MIN:SEC →
??:??
Displays the load shed time (minutes:seconds) delay setting. When
required, use the numeric keys to set the new value. Press the Enter
key.
Returns the user to the load shed output setting.
Displays the corrected load shed time (minutes:seconds) delay
setting.
TIME DELAY MIN:SEC →
##:##
LOAD SHED OUTPUT →
#% # KW
RATED CURRENT #
Displays the generator set rated current as entered data. Note: This
is a read-only display.
Displays the corrected system frequency. See NOTE A.
SYSTEM FREQ # HZ