TP-6200 10/12 19Section 1 Specifications and Features
Engine Displays (Menu 2)
Some engine displays are available with selected
generator set engines using engine ECMs only. The
controller display shows N/A (not available) for items
that are unavailable. See the controller spec sheet for
applicable generator set models.
Ambient Temperature displays the generator set area
ambient temperature.
Charge Air Pressure displays the engine turbocharger
boost air pressure.
Charge Air Temperature displays the engine
turbocharger boost air temperature.
Coolant Level displays the engine coolant level.
Coolant Pressure displays the engine coolant
pressure.
Coolant Temperature displays the engine coolant
temperature.
Crankcase Pressure displays the engine crankcase
pressure.
DC Volts displays the voltage of starting battery(ies).
Fuel Pressure displays the fuel supply pressure.
Fuel Rate displays the calculated fuel consumption rate
based on fuel injector outputs.
Fuel Temperature displays the fuel supply
temperature.
Oil Level displays the engine oil level as a percent of full
capacity.
Oil Pressure displays the engine oil pressure.
Oil Temperature displays the engine oil temperature.
RPM (Tachometer) displays the engine speed.
Used Last Run displays the accumulated amount of
fuel used since last reset by the engine DDEC reader.
Operational Record Displays (Menus 4 and 5)
The operational record displays events since last reset.
See Section 2.8.4, Menu 4—Operational Records, for
resetting procedure.
Engine Start Countdown displays the time remaining
before the next generator set startup.
Event History displays up to 100 stored system events
including status, warnings, and shutdowns.
Last Start Date displays the date when the generator
set last operated.
Number of Starts displays the total number of
generator set startup events.
Number of Starts (Since) Last Maintenance displays
the total number of generator set startup events since
the last maintenance date.
Operating Days (Since) Last Maintenance displays
the total number of days of operation since the last
maintenance date. A counted day of operation can be
1--24 hours.
Run Time displays the total loaded hours, total
unloaded hours, and total kW hours.
Run Time Since Maintenance displays the total loaded
hours, total unloaded hours, and total kW hours.
Time Delay Displays (Menu 8)
The time delays are user adjustable. See Section 2.8.8,
Menu 8—TIme Delays, for time delay adjustments. See
Section 1.3.1, Status Event and Fault Specifications, for
range and default settings.
Crank On/Crank Pause displays the time allocated for
generator set crank on and crank pause in
minutes:seconds.
Engine Cooldown displays the time delay for engine
cooldown while the master switch is in the AUTO or RUN
positions and not in the idle mode.
Engine Start displays the time delay before the
generator set starts while the master switch is in AUTO
or RUN positions.
Overcrank Shutdown (Number of) Crank Cycles
displays the number of unsuccessful crank cycles
(crank on/crank pause) before the generator set shuts
down on an overcrank fault.
Overvoltage displays the time delay before the
generator set shuts down because of an overvoltage
condition.
Starting Aid displays the engine starting aid activation
time.
Undervoltage displays the time delay before the
generator set shuts down because of an undervoltage
condition.