Kohler 20-3250 kW Portable Generator User Manual


 
TP-6200 10/12128 Section 2 Operation
Local Programming Mode On
Menu 13—Communications, continued
Menu 13 Displays with Key Entries
Key
Entry Display Description
BAUD RATES
9600 N/Y
19200 N/Y
BAUD RATE
(USER DEFINED) Y/N
Displays the user-defined baud rate. Press the Down arrow key if the
correct baud rate is displayed. If the desired baud rate is not
displayed, press the Right arrow key until the desired baud rate
appears.
Entering YES selects the baud rate shown. Note: Selecting one
baud rate deselects any previously selected choice.
PROTOCOL
MODBUS
Returns the user to Modbus protocol heading.
Confirms the entry.
BAUD RATE
(USER DEFINED) YES
Press the Enter key.
BAUD RATE
(USER DEFINED) YES
ADDRESS ?
Displays the address number. Use the numeric keys to enter the
desired address 1--128. Use one address number per unit and use
consecutive numbers. Individual addresses are necessary for the
software to call up the desired unit.
Confirms the entry.
ADDRESS #
Confirms the entry.
Press the Enter key.
PRIMARY PORT
(USER DEFINED) YES
PRIMARY PORT
(USER DEFINED) YES