TP-6200 10/12100 Section 2 Operation
Local Programming Mode On
Menu 9—Input Setup
Menu 9 Displays with Key Entries
MAIN MENU NUMBER 9
MENU 9
INPUT SETUP
Key
Entry Display Description
Input a menu number.
Displays the setup of digital auxiliary inputs heading.
Displays the digital input 01 with the user-defined description.
Note: Press the down arrow to move to the start of the next input
setup.
SETUP DIGITAL →
AUXILIARY INPUTS
DIGITAL INPUT 01 →
(USER DEFINED DESC)
Identifies the signal source for digital input 01. Use the menu down ↓
key to select the digital input.
DIGITAL INPUT 01 →
(see Group A) YES/NO
DIGITAL INPUT 01 →
ENABLED YES/NO
Displays the digital input 01, enabled yes or no selection.
Press the Enter key.
DIGITAL INPUT 01 →
ENABLED YES
Confirms the entry.
DIGITAL INPUT 01 →
ENABLED YES
OR
Press the Enter key.
DIGITAL INPUT 01 →
ENABLED NO
Confirms the entry.
DIGITAL INPUT 01 →
ENABLED NO
ENTER MENU NO. 1--15
Press the Enter key.
Displays the menu number and name.
DIGITAL INPUT 01 →
ENABLED NO
Entering YES enables digital input 01.
Entering NO disables digital input 01.
DIGITAL INPUT 01 →
ENABLED YES
Group A
The preprogrammed
selections include the
following list. See
Appendix E for
application and
restrictions with specific
engines.
WARNING Y/N
SHUTDOWN TYPE A Y/N
SHUTDOWN TYPE B Y/N
VOLTAGE RAISE Y/N
VOLTAGE LOWER Y/N
Group A, continued
VAR PF MODE Y/N
REMOTE SHUTDOWN Y/N
REMOTE RESET Y/N
AIR DAMPER Y/N
LOW FUEL Y/N
FIELD OVERVOLTAGE Y/N
IDLE MODE ACTIVE Y/N
BATTLE SWITCH Y/N
GROUND FAULT Y/N
BAT CHGR FAULT Y/N
HIGH OIL TEMP Y/N
Group A, continued
LOW COOLANT LEVEL Y/N
LOW COOLANT TEMP Y/N
BREAKER CLOSED Y/N
ENABLE SYNCH Y/N
AFM SHUTDOWN Y/N
KNOCK SHUTDOWN Y/N
DETON WARNING Y/N
DETON SHUTDOWN Y/N
LOW FUEL SHUTDOWN Y/N