Kohler 20-3250 kW Portable Generator User Manual


 
TP-6200 10/1226 Section 1 Specifications and Features
Factory-Defined Settings
Status Event
or Fault
Time
Delay
(sec.)
Inhibit
Time
Delay
(sec.)
Default
Selection
Range SettingLamp
Alarm
Horn
Relay
Driver
Output
(RDO)
Digital Display
Refer
to
Menu
Digital Aux. Input
D12 Detonation
Warning ]
9, 10 D12
DETON
WARNING
On Warning Fixed 2 sec.
inhibit,
0 sec. delay
Digital Aux. Input
D13 Detonation
Sensing Module
(DSM) Shutdown ]
9, 10 D13
DETON
SHUTDOWN
On Shutdown Fixed 0 sec.
inhibit,
0 sec. delay
Digital Aux. Input
D13 Knock Detection
Module (KDM)
Shutdown ]
9, 10 D13
KNOCK
SHUTDOWN
On Shutdown Fixed 0 sec.
inhibit,
0 sec. delay
Digital Aux. Input D14
Low Coolant Level,
(with LCL switch) **
9, 10 D14 LOW
COOLANT LVL
RDO-19 On Shutdown Fixed 30 sec.
inhibit,
5 sec. delay
Digital Aux. Input
D15 Remote
Shutdown
9, 10 D15 REMOTE
SHUTDOWN
On Shutdown 0 sec.
inhibit,
0 sec. delay
Digital Aux. Input
D16 Remote Reset
9, 10
Digital Aux. Input
D17 VAR/PF mode
9, 10
Digital Aux. Input
D18 Voltage Lower
9, 10
Digital Aux. Input
D19 Voltage Raise
9, 10
Digital Aux. Input
D20 Air Damper
Indicator (if used) **
9, 10 D20
AIR DAMPER
RDO-23 *
(lead 56)
On Shutdown Fixed 0 sec.
inhibit,
0 sec. delay
Digital Aux. Input
D21 Idle (speed)
Mode Function
9, 10 D21
IDLE MODE
ACTIVE
RDO-21 Off Warning Fixed inhibit time 0 sec.
inhibit,
60 sec.
delay
0--600
or 9:99
for
infinity
ECM Red Alarm
(was MDEC Red
Alarm) [[
10 ECM RED
ALARM
On Shutdown
ECM Yellow Alarm
(was MDEC Ye llow
Alarm) [[
10 ECM YELLOW
ALARM
On Warning
EEPROM Write
Failure
10 EEPROM WRITE
FAILURE
On Shutdown
Emergency Stop
Shutdown
10 EMERGENCY
STOP
RDO-14
(lead 48)
On Shutdown
Engine Cooldown
(see Time Delay--)
Engine Derate Active 10 ENGINE
DERATE
ACTIVE
(Engine) J1939 CAN
Shutdown
(ECM only)
10 J1939 CAN
SHUTDOWN
On Shutdown
Engine Stalled
(ECM only)
10 ENGINE
STALLED
On Shutdown
Engine Start
(see Time Delay--)
EPS (Emergency
Power System)
Supplying Load
10 EPS
SUPPLYING
LOAD
RDO-22 Off Warning Fixed 1% of rated
line current
Field Overvoltage
(see D04)
* All models, except Waukesha-powered models. ** NFPA applications
[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC
] Waukesha-powered models ]] FAA only
w Paralleling applications