Kohler 20-3250 kW Portable Generator User Manual


 
TP-6200 10/12 115Section 2 Operation
Local Programming Mode On
Menu 11—Voltage Regulator, continued
Menu 11 Displays with Key Entries
Key
Entry Display Description
UNDER FREQ UNLOAD
ENABLED N/Y
Displays the under frequency (volts per Hz) unloading (yes or no)
selection.
Press the Enter key.
Confirms the entry.
UNDER FREQ UNLOAD
ENABLED YES
UNDER FREQ UNLOAD
ENABLED YES
UNDER FREQ UNLOAD
ENABLED NO
Entering YES enables the underfrequency unloading feature.
OR
Confirms the entry.
Press the Enter key.
UNDER FREQ UNLOAD
ENABLED NO
UNDER FREQ UNLOAD
ENABLED NO
Entering NO disables the underfrequency unloading feature.
UNDER FREQ UNLOAD
ENABLED YES
FREQUENCY # HZ
SETPOINT ?.? HZ
Displays the present operating frequency and underfrequency
unloading cut-in point. Enter the desired underfrequency cut-in point
using the numeric keys. Press the Menu Right
key prior to
entering the decimal value.
Confirms the entry.
FREQUENCY # HZ
SETPOINT #.# HZ
AND
FREQUENCY # HZ
SETPOINT ?.? HZ
Use the numeric keys to enter the decimal value. Press the Enter
key.
SLOPE
?.? VOLTS-PER-CYCLE
Displays the underfrequency unloading slope (volts-per-cycle). Enter
the desired underfrequency unloading slope using the numeric keys.
Press the Menu Right
key prior to entering the decimal value.
Confirms the entry.
SLOPE
#.# VOLTS-PER-CYCLE
AND
Use the numeric keys to enter the decimal value. Press the Enter
key.
SLOPE
?.? VOLTS-PER-CYCLE
UNDER FREQ UNLOAD
ENABLED N/Y
Returns the user to the underfrequency unloading heading.