TP-6200 10/1270 Section 2 Operation
2.7.15 Menu 15—Protective Relays (PR)
Menu 15 provides protective relay setup and time delays
for units with the paralleling protection option. This
menu will only be v isible and accessible if this option is
included. The shutdown (SD) settings override those in
menu 7 and/or menu 8.
See Section 2.8.15 to make changes in this menu, when
the paralleling option is enabled.
MENU 15
PROTECTIVE RELAYS
PR OVERVOLTAGE →
?% # VAC
TIME DELAY →
? SEC
Menu 15 Overview
PR UNDERVOLTAGE →
?% # VAC
TIME DELAY →
? SEC
PR OVERFREQUENCY →
?% # HZ
TIME DELAY →
? SEC
TIME DELAY →
? SEC
PR UNDERFREQUENCY →
?% # HZ
PR REVERSE POWER →
?% # KW
TIME DELAY →
? SEC
SD REVERSE POWER →
?% # KW
TIME DELAY →
? SEC
PR OVER POWER →
?% # KW
TIME DELAY →
? SEC
SD OVER POWER →
?% # KW
TIME DELAY →
? SEC
TIME DELAY →
? SEC
PR LOSS OF FIELD →
?% # KVAR
SD LOSS OF FIELD →
?% # KVAR
TIME DELAY →
? SEC
PR OVER CURRENT VR →
?% # AMPS
TIME DELAY →
? SEC
TIME DELAY →
? SEC
SD OVER CURRENT VR →
?% # AMPS
SYNC FREQ MATCH →
?HZ
SYNC VOLTAGE MATCH →
?VAC
SYNC PHASE MATCH →
?DEG
TIME DELAY →
? SEC