TP-6200 10/12106 Section 2 Operation
Local Programming Mode On
Menu 10—Output Setup, continued
Menu 10 Displays with Key Entries
Key
Entry Display Description
DIGITAL INPUTS →
Displays the digital inputs heading.
Gives the user the option to add or delete selection from the defined
digital faults starting with D01. Note: Press the Menu Down key to
continue to the next selection D02--D21 (repeat as necessary).
COMMON FAULT Y/N
Dxx (see Group C)
OR
COMMON FAULT YES
Dxx (see Group C)
COMMON FAULT YES
Dxx (see Group C)
COMMON FAULT NO
Dxx (see Group C)
COMMON FAULT NO
Dxx (see Group C)
Press the Enter key.
Confirms the entry.
Press the Enter key.
Confirms the entry.
ANALOG INPUTS →
Displays the analog inputs heading.
COMMON FAULT Y/N
Axx
(see Group D) LO
WARNING→
Gives the user the option to add or delete selection from the defined
analog faults starting with A01. Note: Press the Menu Down key to
continue to the next selection A02--A07 (repeat as necessary).
COMMON FAULT NO
Dxx (see Group C)
Entering YES adds the selection to the defined digital fault group.
COMMON FAULT YES
Dxx (see Group C)
Entering NO removes the selection from the defined digital fault
group.
Group C
Up to 21 PC user-defined digital
status and fault inputs designated
as D01 to D21 can result in an
digital input common fault.
Group D
Up to 7 analog inputs, PC user-
defined status events and faults
designated as A01 to A07.
Each of the 7 is assignable as a
shutdown or warning with high
and low settings.