TP-6200 10/12118 Section 2 Operation
Local Programming Mode On
Menu 11—Voltage Regulator, continued
Menu 11 Displays with Key Entries
Key
Entry Display Description
Displays the power factor control selection (yes or no).
PF CONTROL →
ENABLED N/Y
Entering YES enables the power factor control feature.
Note: A YES entry disables the kVAR control if previously activated.
Confirms the entry.
PF CONTROL →
ENABLED NO
PF CONTROL →
ENABLED YES
Press the Enter key.
PF CONTROL →
ENABLED YES
OR
Confirms the entry.
Press the Enter key.
PF CONTROL →
ENABLED NO
PF CONTROL →
ENABLED NO
AVERAGE PF #→
PF ADJ ?.?
Displays the present running average power factor and power factor
adjustment settings. Enter the desired kVAR adjustment using the
numeric keys. Press the Menu Right
→ key prior to entering the
decimal value.
Entering NO disables the power factor control feature.
PF CONTROL →
ENABLED YES
AND
Use the numeric keys to enter the decimal value. Press the Enter
key.
Confirms the entry.
AVERAGE PF #→
PF ADJ #.#
AVERAGE PF #→
PF ADJ ?.?
LAGGING/ N/Y→
LEADING
Displays the lagging or leading PF selection.
Note: The display sample may differ depending upon the previous
entries. The lagging selection is the factory default setting.
Displays the lagging PF selection. When required, use the NO key to
choose leading PF.
Confirms the entry.
LAGGING YES→
LEADING YES→
Press the Enter key.
LAGGING NO→
OR
Confirms the entry.
LEADING YES→
LEADING NO→
LAGGING YES→
Displays the leading PF selection. When required, use the NO key to
choose lagging PF.
Press the Enter key.
PF CONTROL →
ENABLED N/Y
Returns the user to the power factor control selection heading.