Kohler 20-3250 kW Portable Generator User Manual


 
TP-6200 10/12 75Section 2 Operation
Local Programming Mode On
2.8.1 Menu 1—Generator Monitoring
Menu 1 provides generator output data including
line-to-line and line-to-neutral voltages, current,
frequency, power factor, total kilowatts, percent of
maximum kW, total kVA and total kVAR displays.
Menu 1 displays three-phase and single-phase
connections separately.
Note: For the auto-scroll function, press ENTER at the
V & A Summary menu. Press the Reset Menu
key or Menu Right key to stop the auto-scroll
function.
Note: A right arrow from any submenu moves to the
next submenu header.
Menu 1—Generator Monitoring (Three-Phase Connections)
Menu 1 Displays with Key Entries
Note: This menu is for monitoring only; no adjustments or user settings can be entered.
Key Entry Display Description
ENTER MENU NO. 1--15
Input a menu number.
Press the Enter key.
Displays the volts and amps heading.
VOLTS & AMPS
L1-L2 VOLTS #
L1 AMPS #
Displays L1 and L2 volts and L1 amps.
L2-L3 VOLTS #
L2 AMPS #
Displays L2 and L0 volts and L2 amps.
L2-L0 VOLTS #
L2 AMPS #
L1-L0 VOLTS #
L1 AMPS #
Displays L1-L0 volts and L1 amps.
FREQUENCY # HZ
Displays the frequency.
L3-L0 VOLTS #
L3 AMPS #
Displays L3-L0 volts and L3 amps.
Displays L2 and L3 volts and L2 amps.
Displays L3 and L1 volts and L3 amps.
L3-L1 VOLTS #
L3 AMPS #
Returns the user to volts and amps heading.
VOLTS & AMPS
MENU 1
GENERATOR MONITORING
Displays the menu number and name.
MAIN MENU NUMBER 1
V&ASUMMARY
Displays the volts and amps summary heading.
Displays L1-L2, L2-L3, and L3-L1 volts.
V L1-L2 L2-L3 L3-L1
###
MENU 1
GENERATOR MONITORING
Returns the user to the menu number and name.
Displays L1-L0, L2-L0, and L3-L0 volts. (3 ph. only)
V L1-L0 L2-L0 L3-L0
###