Kohler 20-3250 kW Portable Generator User Manual


 
TP-6200 10/12 Appendix 197
Status Event
or Fault
User-Defined
Settings
Time
Delay
(sec.)
Inhibit
Time
Delay
(sec.)
Default
Selection
Range Setting
Relay
Driver
Output
(RDO)
Digital Display
Refer
to
Menu
Digital Aux. Input
D05 Breaker
Closed w
9, 10 D05
BREAKER
CLOSED
Fixed 0 sec.
inhibit,
0 sec. delay
Not adjustable
Digital Aux. Input
D06 w
9, 10 D06 ENABLE
SYNCH
20 sec.
inhibit,
0 sec. delay
Not adjustable
Digital Aux. Input
D09 Low Fuel
Pressure Shutdown
(125RZG only)
9, 10 D09
LOW FUEL
SHUTDOWN
Fixed 5 sec.
inhibit,
0 sec. delay
Not adjustable
Digital Aux. Input
D11 Air/Fuel Module
(AFM) Shutdown ]
9, 10 D11
AFM
SHUTDOWN
Fixed 0 sec.
inhibit,
0 sec. delay
Not adjustable
Digital Aux. Input
D12 Detonation
Warning ]
9, 10 D12
DETON
WARNING
Fixed 2 sec.
inhibit,
0 sec. delay
Not adjustable
Digital Aux. Input
D13 Detonation
Sensing Module
(DSM) Shutdown ]
9, 10 D13
DETON
SHUTDOWN
Fixed 0 sec.
inhibit,
0 sec. delay
Not adjustable
Digital Aux. Input
D13 Knock Detection
Module (KDM)
Shutdown ]
9, 10 D13
KNOCK
SHUTDOWN
Fixed 0 sec.
inhibit,
0 sec. delay
Not adjustable
Digital Aux. Input D14
Low Coolant Level,
(with LCL switch) **
9, 10 D14 LOW
COOLANT LVL
RDO-19 Fixed 30 sec.
inhibit,
5 sec. delay
Not adjustable
Digital Aux. Input
D15 Remote
Shutdown
9, 10 D15 REMOTE
SHUTDOWN
0 sec.
inhibit,
0 sec. delay
Not adjustable
Digital Aux. Input
D16 Remote Reset
9, 10 Not adjustable
Digital Aux. Input
D17 VAR/PF mode
9, 10 Not adjustable
Digital Aux. Input
D18 Voltage Lower
9, 10 Not adjustable
Digital Aux. Input
D19 Voltage Raise
9, 10 Not adjustable
Digital Aux. Input
D20 Air Damper
Indicator (if used) **
9, 10 D20
AIR DAMPER
RDO-23 *
(lead 56)
Fixed 0 sec.
inhibit,
0 sec. delay
Not adjustable
Digital Aux. Input
D21 Idle (speed)
Mode Function
9, 10 D21
IDLE MODE
ACTIVE
RDO-21 Fixed inhibit time 0 sec.
inhibit,
60 sec.
delay
0--600
or 9:99
for
infinity
Not adjustable
ECM Red Alarm
(was MDEC Yellow
Alarm) [[
10 ECM RED ALARM Not adjustable
ECM Yellow Alarm
(was MDEC Yellow
Alarm) [[
10 ECM YELLOW
ALARM
Not adjustable
EEPROM Write
Failure
10 EEPROM WRITE
FAILURE
Not adjustable
Emergency Stop
Shutdown
10 EMERGENCY
STOP
RDO-14
(lead 48)
Not adjustable
Engine Cooldown
(see Time Delay--)
Engine Derate Active 10 ENGINE DERATE
ACTIVE
Not adjustable
* All models, except Waukesha-powered models. ** NFPA applications
[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC
] Waukesha-powered models ]] FAA only
w Paralleling applications