TP-6200 10/12 101Section 2 Operation
Local Programming Mode On
Menu 9—Input Setup, continued
Menu 9 Displays with Key Entries
Key
Entry Display Description
DIGITAL INPUT 01 →
DELAY TIME ?:??
Displays the digital input 01 delay time (minutes:seconds) setting.
When required, use the numeric keys to set the new values. Press
the Enter key.
Displays the digital input 01 inhibit time (minutes:seconds) setting.
When required, use the numeric keys to set the new values. Press
the Enter key.
DIGITAL INPUT 01 →
INHIBIT TIME ?:??
Displays the corrected inhibit time (minutes:seconds) setting.
DIGITAL INPUT 01
INHIBIT TIME #:##
Displays the corrected delay time (minutes:seconds) setting.
DIGITAL INPUT 01 →
DELAY TIME #:##
DIGITAL INPUT 01 →
(USER DEFINED DESC)
Returns the user to digital input 01.
DIGITAL INPUT XX →
(USER DEFINED DESC)
Displays digital inputs 02 to 21. Note: Press the down arrow to scroll
through additional digital auxiliary inputs or enter the input number.
Note: Press the right arrow at each digital auxiliary input to enable the
selection, inhibit time setting, and delay time setting. See Digital
Input 01 instructions for complete procedure and Group A
selections.See Figure 2-8 in User Inputs for factory reserved digital
and analog inputs which are not user selectable.
Returns the user to setup digital auxiliary inputs.
SETUP DIGITAL →
AUXILIARY INPUTS
SETUP ANALOG →
AUXILIARY INPUTS
Displays the setup of analog auxiliary inputs heading.
ANALOG INPUT 01 →
(USER DEFINED DESC)
ANALOG INPUT 01 →
WARNING ENABLED Y/N
Displays the analog input 01 with user-defined description.
Note: ECM engines have inputs 01 --07 and non-ECM engines have
inputs 03--07. Waukesha engines have inputs 05--07. Note: Press
the down arrow to move to the start of the next input setup.
Displays the analog input 01, warning enabled yes or no selection.
Press the Enter key.
ANALOG INPUT 01 →
WARNING ENABLED YES
AND
Confirms the entry.
ANALOG INPUT 01 →
WARNING ENABLED YES
OR
Press the Enter key.
ANALOG INPUT 01 →
WARNING ENABLED NO
AND
Confirms the entry.
ANALOG INPUT 01 →
WARNING ENABLED NO
Entering YES enables the warning analog input 01.
ANALOG INPUT 01 →
WARNING ENABLED NO
Entering NO disables the warning analog input 01.
ANALOG INPUT 01 →
WARNING ENABLED YES
MENU 9
INPUT SETUP
Returns the user to the menu number and name.