TP-6200 10/12 173Section 6 Accessories
6.1.9 Remote Emergency Stop Kit
The emergency stop kit allows immediate shutdown of
the generator set from a remote location. See
Figure 6-14 and Figure 6-15. If the emergency stop
switch activates, the EMERGENCY STOP lamp lights
and the unit shuts down. Before attempting to restart the
generator set, reset the emergency stop switch (by
replacing the glass piece) and reset the generator set by
placing the master switch in the OFF/RESET position.
Use the single glass piece located inside the switch for
replacement and order additional glass pieces as
service parts. See Section 2.3.3, Emergency Stop
Switch Reset Procedure. See Section 6.2, Accessory
Connections, for terminal identifications.
A-222654
TP-5352-1
Figure 6-14 Emergency Stop Kit
GM16088A-A
Figure 6-15 Remote Emergency Stop Kit
Connections
6.1.10 Remote Reset Feature
The remote reset switch provides generator set
resetting after a fault shutdown at a remote location. See
Figure 6-16 and Figure 6-17 for user-supplied switch
connection.
Press and hold the switch for 2--3 seconds and release
to reset the generator set controller.
REMOTE RESET SWITCH
CONTACTS NORMALLY OPEN
MOMENTARY CLOSED TO
ACTIVATE
GM16088A-A-
≈
Figure 6-16 Remote Reset Switch Connections
Switch Rating 12 volts DC minimum, 1 amp minimum
Wiring Recommendation
Gauge mm (ft.)
18--20 30.5 (100)
14 153 (500)
10 305 (1000)
Figure 6-17 Switch Rating and Wiring
Recommendations