Kohler 20-3250 kW Portable Generator User Manual


 
TP-6200 10/12 123Section 2 Operation
Local Programming Mode On
Menu 12—Calibration, continued
Menu 12 Displays with Key Entries (Scale AC Analog Inputs)
Key
Entry Display Description
GEN L3 AMPS #
CALIB REF ?.?
Three-Phase Models only. Measure the generator set output
current for three-phase models at L3 using an AC ammeter and enter
the result using the numeric keys. Press the Menu Right
key prior
to entering the decimal value.
AND
Use the numeric keys to enter the decimal value. Press the Enter
key.
GEN L3 AMPS #
CALIB REF ?.?
Confirms the entry.
GEN L3 AMPS #
CALIB REF #
Returns the user to the generator set amps heading.
GEN AMPS
RESTORE DEFAULTS? Y/N
Displays the restore defaults selection.
Displays the load voltage line-to-neutral voltage heading.
LOAD VOLTAGE LN
LOADL1--L0V #
CALIB REF (PARALLEL) ?.?
Note: The generator sets must be running for the following steps.
Paralleling Applications. Measure the load voltage between L1-L0
using a voltmeter and enter the result using the numeric keys. Press
the Menu Right key prior to entering the decimal value.
Confirms the entry.
GEN L1-L0 V #
CALIB REF #
AND
Use the numeric keys to enter the decimal value. Press the Enter
key.
GEN L1-L0 V #
CALIB REF ?.?
LOADL3--L0V #
CALIB REF (PARALLEL) ?.?
Note: The generator sets must be running for the following steps.
Paralleling Applications. Measure the load voltage for three-phase
models between L3-L0 using a voltmeter and enter the result using
the numeric keys. Press the Menu Right key prior to entering the
decimal value.
Confirms the entry.
GEN L3-L0 V #
CALIB REF #
AND
Use the numeric keys to enter the decimal value. Press the Enter
key.
GEN L3-L0 V #
CALIB REF ?.?
Returns the user to the load voltage line-to-neutral voltage heading.
LOAD VOLTAGE LN
When required, enter YES to activate the restore calibration defaults
setting. Press the Enter key. Note: Entering Yes will delete all of the
previously entered voltage and current data based on system voltage
and kW and restore the calibration default settings.
Confirms the entry.
RESTORE DEFAULTS? YES
RESTORE DEFAULTS? Y/N
Returns the user to the generator set voltage line-to-neutral heading.
GEN VOLTAGE LN