Kohler 20-3250 kW Portable Generator User Manual


 
TP-6200 10/1228 Section 1 Specifications and Features
Factory-Defined Settings
Status Event
or Fault
Time
Delay
(sec.)
Inhibit
Time
Delay
(sec.)
Default
Selection
Range SettingLamp
Alarm
Horn
Relay
Driver
Output
(RDO)
Digital Display
Refer
to
Menu
Locked Rotor
Shutdown
10 LOCKED
ROTOR
On Shutdown
Loss of ECM
Communication
(ECM only)
10 LOSS OF ECM
COMM
RDO-26 * On Shutdown 4
Loss of Field
Shutdown w
10 SD LOSS OF
FIELD
On Shutdown
Low Battery Voltage 10 LOW BATTERY
VOLTAGE
RDO-12
(lead 62)
Off Warning 10--12.5 V (12 V)
20--25 V (24 V)
12 V (12 V)
24 V (24 V)
0 10
Low Coolant Level
(see D14) (with LCL
switch) **
Low Coolant
Temperature (see
D03) **
Low Coolant
Temperature
Shutdown [[
10 LOW COOLANT
TEMP
SHUTDOWN
On Shutdown
Low Fuel (Level or
Pressure) Warning
(see D02) **
Low Fuel Pressure
Shutdown (see D09)
(125RZG only)
(Low) Oil Pressure
Shutdown
10 OIL
PRESSURE
SHUTDOWN
RDO-04
(lead 38)
On Shutdown 30 5
(Low) Oil Pressure
Warning
10 OIL
PRESSURE
WARNING
RDO-07
(lead 41)
On Warning 30
Maintenance Due 10 MAINTENANCE
DUE
Master Not In Auto
(Generator Set
Switch)
10 MASTER NOT
IN AUTO
RDO-09
(lead 80)
On Warning
and Not
In Auto
Master Switch Error 10 MASTER
SWITCH
ERROR
On Shutdown
Master Switch to Off 10 MASTER
SWITCH TO
OFF
On Shutdown
and Not
in Auto
Master Switch Open 10 MASTER
SWITCH OPEN
On Shutdown
NFPA 110 Fault ** 10 NFPA 110
FAULT
RDO-10
(lead 32)
On Shutdown
or
Warning
No Air Temperature
Signal Warning ]
10 NO AIR TEMP
SIGNAL
On Warning 30 4
No Coolant
Temperature Signal
10 NO COOL
TEMP SIGNAL
On Shutdown 30 4
No Oil Pressure
Signal
10 NO OIL
PRESSURE
SIGNAL
On Shutdown 30 4
No Oil Temperature
Signal Warning ]
10 NO OIL TEMP
SIGNAL
On Warning 30 4
Overcrank Shutdown 8, 10 OVER CRANK RDO-02
(lead 12)
On Shutdown 0--6 Cycles 3 Cycles
* All models, except Waukesha-powered models. ** NFPA applications
[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC
] Waukesha-powered models ]] FAA only
w Paralleling applications