Kohler 20-3250 kW Portable Generator User Manual


 
TP-6200 10/1286 Section 2 Operation
Local Programming Mode On
2.8.4 Menu 4—Operational Records
Menu 4 provides the generator set operational records
including the operating start date, last logged
maintenance, total run time loaded and unloaded, run
time since the last maintenance, number of starts, and
number of running days.
Run Time Feature. This menu provides the ability t o r un
the generator set for a designated time. After the run time
elapses. the generator set shuts down and functions in
the standby mode. The generator set controller does not
provide weekly scheduled exercise periods.
Generator set connected to an automatic transfer
switch. Should a utility power failure occur while the unit
is in the run time mode, the controller bypasses the run
time mode and functions in the standby (backup) mode.
If the utility power returns, the generator set continues to
run for the duration of the run time period if not timed out.
Note: Press the STOP PROG RUN key to stop the
generator set when in the run time mode, if
necessary.
After performing maintenance, enter yes to reset
records reflecting the current day. The user must enable
the programming mode to edit the display.
Menu 4—Operational Records
Menu 4 Displays with Key Entries
Key
Entry Display Description
Input a menu number.
MENU 4
OPERATIONAL RECORDS
Displays the total run time (hours:minutes).
Displays the total run time for loaded hours.
Displays the total run time for unloaded hours.
Displays the total run time in kW hours.
TOTAL RUN TIME
HRS #
TOTAL RUN TIME
LOADED HRS #
TOTAL RUN TIME
UNLOADED HRS #
TOTAL RUN TIME
KW HRS #
NO. OF STARTS #
Displays the number of engine starts.
Displays the start and countdown subheading.
ENGINE START? Y/N
COUNTDOWN ##:##
RUN TIME HR:MN
??:??
Displays the run time (hours:minutes) feature. When required, use
the numeric keys to enter the selected run time (hours:minutes) and
press the Enter key.
Confirms entry and displays the selected run time (hours:minutes).
The generator set will start after activation. Note: Activate the
generator set run time feature by pressing the Yes and Enter keys.
See the following steps.
FACTORY TEST DATE
##-###-##
Displays the factory test date (day-month-year).
ENGINE START? Y/N
COUNTDOWN ##:##
Returns the user to the start and countdown subheading. Enter Yes
to start the generator set.
RUN TIME HR:MN
##:##
ENTER MENU NO. 1--15
Press the Enter key.
Displays the menu number and name.
MAIN MENU NUMBER 4