Kohler 20-3250 kW Portable Generator User Manual


 
TP-6200 10/12134 Section 2 Operation
Local Programming Mode On
Menu 15—Protective Relays, continued
Menu 15 Displays with Key Entries
Key
Entry Display Description
Displays the over current shutdown with voltage restraint (VR) %
value. When required, use the numeric keys to enter the desired over
current shutdown % value and press the Enter key.
SD OVER CURRENT VR
?% #AMPS
Displays the corrected over current shutdown % value.
SD OVER CURRENT VR
#% #AMPS
Displays the over current shutdown time delay. When required, use
the numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY
?SEC
Displays the corrected over current shutdown time delay value.
TIME DELAY
#SEC
SD OVER CURRENT VR
?% #AMPS
Returns the user to the over current shutdown % value display.
Displays the synchronization matching voltage value. When required,
use the numeric keys to enter the desired synchronization matching
voltage value and press the Enter key.
SYNC VOLTAGE MATCH
?VAC
Displays the corrected synchronization matching voltage value.
Displays the synchronization time delay. When required, use the
numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY
?SEC
Displays the corrected synchronization time delay value.
TIME DELAY
#SEC
Returns the user to the synchronization matching voltage value
display.
SYNC VOLTAGE MATCH
#VAC
Displays the synchronization matching frequency value. When
required, use the numeric keys to enter the desired synchronization
matching frequency value and press the Enter key.
SYNC FREQ MATCH
?HZ
SYNC FREQ MATCH
#HZ
Displays the corrected synchronization matching frequency value.
Displays the synchronization matching phase value. When required,
use the numeric keys to enter the desired synchronization matching
phase value and press the Enter key.
SYNC PHASE MATCH
?DEG
SYNC FREQ MATCH
#DEG
Displays the corrected synchronization matching phase value.
SYNC VOLTAGE MATCH
?VAC