TP-6200 10/12 57Section 2 Operation
2.7.3 Menu 3—Analog Monitoring
Menu 3 displays battery voltage and up to 7 user-
defined analog items dependent upon the generator
system.
The User Defined Desc display refers to a description
entered into the controller using the PC software. This
description remains as the display for future review until
changed by the PC software user. The display has
20 characters maximum.
The default description is Analog Auxiliary In.
MENU 3
ANALOG MONITORING
LOCAL BATT VDC #
ANALOG 01 #
(USER DEFINED DESC)
ANALOG 02 #
(USER DEFINED DESC)
ANALOG 03 #
(USER DEFINED DESC)
ANALOG 04 #
(USER DEFINED DESC)
Menu 3 Overview (ECM Engines)
ANALOG 05 #
(USER DEFINED DESC)
ANALOG 06 #
(USER DEFINED DESC)
ANALOG 07 #
(USER DEFINED DESC)
Note: If the analog display shows O/R (out of range), no
input is connected or the input voltage is beyond
the acceptable operating range (0--5 VDC).
Note: See Figure 2-8 in User Inputs for factory
reserved inputs which are not user selectable.
MENU 3
ANALOG MONITORING
LOCAL BATT VDC #
ANALOG 03 #
(USER DEFINED DESC)
ANALOG 04 #
(USER DEFINED DESC)
Menu 3 Overview (Non-ECM Engines)
ANALOG 05 #
(USER DEFINED DESC)
ANALOG 06 #
(USER DEFINED DESC)
ANALOG 07 #
(USER DEFINED DESC)
MENU 3
ANALOG MONITORING
LOCAL BATT VDC #
Menu 3 Overview (Waukesha Engines)
ANALOG 05 #
(USER DEFINED DESC)
ANALOG 06 #
(USER DEFINED DESC)
ANALOG 07 #
(USER DEFINED DESC)