TP-6200 10/12122 Section 2 Operation
Local Programming Mode On
Menu 12—Calibration, continued
Menu 12 Displays with Key Entries (Scale AC Analog Inputs)
Key
Entry Display Description
GEN L3-L1 V #
CALIB REF ?.?
Three-Phase Models only. Measure the generator set output
voltage for three-phase models between L3-L1 using a voltmeter and
enter the result using the numeric keys. Press the Menu Right
→ key
prior to entering the decimal value.
Confirms the entry.
GEN L3-L1 V #
CALIB REF #
AND
Use the numeric keys to enter the decimal value. Press the Enter
key.
GEN L3-L1 V #
CALIB REF ?.?
GEN VOLTAGE LL
Returns the user to the generator set line-to-line voltage heading.
Displays the generator set amps heading.
GEN AMPS
GEN L1 AMPS #
CALIB REF ?.?
Note: The generator set must be running for the following steps.
Measure the generator set output current for single - and three-phase
models at L1 using an AC ammeter and enter the result using the
numeric keys. Press the Menu Right → key prior to entering the
decimal value.
Confirms the entry.
GEN L1 AMPS #
CALIB REF #
AND
Use the numeric keys to enter the decimal value. Press the Enter
key.
GEN L1 AMPS #
CALIB REF ?.?
GEN L2 AMPS #
CALIB REF ?.?
Measure the generator set output current for three-phase models at
L2 using an AC ammeter and enter the result using the numeric keys.
Press the Menu Right
→ key prior to entering the decimal value.
Confirms the entry.
GEN L2 AMPS #
CALIB REF #
AND
Use the numeric keys to enter the decimal value. Press the Enter
key.
GEN L2 AMPS #
CALIB REF ?.?
CALIBRATE REGULATOR?
Y/N
Displays the calibrate regulator selection.
Note: After changing the meter calibration the voltage regulator
should be calibrated—enter YES.
When required, use the YES key to calibrate the voltage regulator.
Confirms the entry.
CALIBRATE REGULATOR?
YES
CALIBRATE REGULATOR?
Y/N