Kohler 20-3250 kW Portable Generator User Manual


 
TP-6200 10/12116 Section 2 Operation
Local Programming Mode On
Menu 11—Voltage Regulator, continued
Menu 11 Displays with Key Entries
Key
Entry Display Description
Displays the reactive droop selection (yes or no).
REACTIVE DROOP
ENABLED N/Y
OR
Press the Enter key.
Confirms the entry.
Confirms the entry.
Press the Enter key.
REACTIVE DROOP
ENABLED YES
REACTIVE DROOP
ENABLED YES
REACTIVE DROOP
ENABLED NO
REACTIVE DROOP
ENABLED NO
Entering YES enables the reactive droop feature.
REACTIVE DROOP
ENABLED NO
Entering NO disables the reactive droop feature.
REACTIVE DROOP
ENABLED YES
.8 PF RATED LOAD
VOLTAGE DROOP ?.?%
Displays the reactive (voltage) droop as a percentage of the rated
voltage at rated load. When required, enter the desired reactive
droop using the numeric keys. Press the Menu Right
key prior to
entering the decimal value.
Confirms the entry.
.8 PF RATED LOAD
VOLTAGE DROOP #.#%
AND
Use the numeric keys to enter the decimal value. Press the Enter
key.
.8 PF RATED LOAD
VOLTAGE DROOP ?.?%