TP-6200 10/12116 Section 2 Operation
Local Programming Mode On
Menu 11—Voltage Regulator, continued
Menu 11 Displays with Key Entries
Key
Entry Display Description
Displays the reactive droop selection (yes or no).
REACTIVE DROOP →
ENABLED N/Y
OR
Press the Enter key.
Confirms the entry.
Confirms the entry.
Press the Enter key.
REACTIVE DROOP →
ENABLED YES
REACTIVE DROOP →
ENABLED YES
REACTIVE DROOP →
ENABLED NO
REACTIVE DROOP →
ENABLED NO
Entering YES enables the reactive droop feature.
REACTIVE DROOP →
ENABLED NO
Entering NO disables the reactive droop feature.
REACTIVE DROOP →
ENABLED YES
.8 PF RATED LOAD →
VOLTAGE DROOP ?.?%
Displays the reactive (voltage) droop as a percentage of the rated
voltage at rated load. When required, enter the desired reactive
droop using the numeric keys. Press the Menu Right
→ key prior to
entering the decimal value.
Confirms the entry.
.8 PF RATED LOAD →
VOLTAGE DROOP #.#%
AND
Use the numeric keys to enter the decimal value. Press the Enter
key.
.8 PF RATED LOAD →
VOLTAGE DROOP ?.?%