TP-6200 10/12 133Section 2 Operation
Local Programming Mode On
Menu 15—Protective Relays, continued
Menu 15 Displays with Key Entries
Key
Entry Display Description
Displays the loss of field % value. When required, use the numeric
keys to enter the desired loss of field % value and press the Enter
key.
PR LOSS OF FIELD →
?% #KVAR
Displays the corrected loss of field % value.
PR LOSS OF FIELD →
#% #KVAR
Displays the loss of field time delay. When required, use the numeric
keys to enter the desired time delay value and press the Enter key.
TIME DELAY →
?SEC
Displays the corrected loss of field time delay value.
TIME DELAY →
#SEC
PR LOSS OF FIELD →
?% #KVAR
Returns the user to the loss of field % value display.
Displays the over power shutdown % value. When required, use the
numeric keys to enter the desired over power shutdown % value and
press the Enter key.
SD OVER POWER →
?% #KW
Displays the corrected over power shutdown % value.
SD OVER POWER →
#% #KW
Displays the over power shutdown time delay. When required, use
the numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY →
?SEC
Displays the corrected over power shutdown time delay value.
TIME DELAY →
#SEC
SD OVER POWER →
?% #KW
Returns the user to the over power shutdown % value display.
Displays the loss of field shutdown % value. When required, use the
numeric keys to enter the desired loss of field % value and press the
Enter key.
SD LOSS OF FIELD →
?% #KVAR
Displays the corrected loss of field shutdown % value.
SD LOSS OF FIELD →
#% #KVAR
Displays the loss of field shutdown time delay. When required, use
the numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY →
?SEC
Displays the corrected loss of field shutdown time delay value.
TIME DELAY →
#SEC
SD LOSS OF FIELD →
?% #KVAR
Returns the user to the loss of field shutdown % value display.
Displays the over current with voltage restraint (VR) % value. When
required, use the numeric keys to enter the desired over current %
value and press the Enter key.
PR OVERCURRENT VR →
?% #AMPS
Displays the corrected over current % value.
PR OVERCURRENT VR →
#% #AMPS
Displays the over current time delay. When required, use the numeric
keys to enter the desired time delay value and press the Enter key.
TIME DELAY →
?SEC
Displays the corrected over current time delay value.
TIME DELAY →
#SEC
PR OVERCURRENT VR →
?% #AMPS
Returns the user to the over current % value display.