TP-6200 10/12 133Section 2 Operation
Local Programming Mode On
Menu 15—Protective Relays, continued
Menu 15 Displays with Key Entries
Key
Entry Display Description
Displays the loss of field % value. When required, use the numeric
keys to enter the desired loss of field % value and press the Enter
key.
PR LOSS OF FIELD
?% #KVAR
Displays the corrected loss of field % value.
PR LOSS OF FIELD
#% #KVAR
Displays the loss of field time delay. When required, use the numeric
keys to enter the desired time delay value and press the Enter key.
TIME DELAY
?SEC
Displays the corrected loss of field time delay value.
TIME DELAY
#SEC
PR LOSS OF FIELD
?% #KVAR
Returns the user to the loss of field % value display.
Displays the over power shutdown % value. When required, use the
numeric keys to enter the desired over power shutdown % value and
press the Enter key.
SD OVER POWER
?% #KW
Displays the corrected over power shutdown % value.
SD OVER POWER
#% #KW
Displays the over power shutdown time delay. When required, use
the numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY
?SEC
Displays the corrected over power shutdown time delay value.
TIME DELAY
#SEC
SD OVER POWER
?% #KW
Returns the user to the over power shutdown % value display.
Displays the loss of field shutdown % value. When required, use the
numeric keys to enter the desired loss of field % value and press the
Enter key.
SD LOSS OF FIELD
?% #KVAR
Displays the corrected loss of field shutdown % value.
SD LOSS OF FIELD
#% #KVAR
Displays the loss of field shutdown time delay. When required, use
the numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY
?SEC
Displays the corrected loss of field shutdown time delay value.
TIME DELAY
#SEC
SD LOSS OF FIELD
?% #KVAR
Returns the user to the loss of field shutdown % value display.
Displays the over current with voltage restraint (VR) % value. When
required, use the numeric keys to enter the desired over current %
value and press the Enter key.
PR OVERCURRENT VR
?% #AMPS
Displays the corrected over current % value.
PR OVERCURRENT VR
#% #AMPS
Displays the over current time delay. When required, use the numeric
keys to enter the desired time delay value and press the Enter key.
TIME DELAY
?SEC
Displays the corrected over current time delay value.
TIME DELAY
#SEC
PR OVERCURRENT VR
?% #AMPS
Returns the user to the over current % value display.