TP-6200 10/1264 Section 2 Operation
2.7.10 Menu 10—Output Setup
Menu 10 displays the setup of user-defined system,
digital and analog status, and fault outputs and relay
driver outputs (RDO) 1--31. These RDO outputs provide
multiple choices for configuring customized auxiliary
outputs. Additional individual outputs are available for
monitoring, diagnostics, and control functions.
The user must enable the programming mode to edit the
display. See Section 2.8.10 to change this menu.
Note: Some data require entry using a PC in the
Remote Programming mode. See the Monitor
Software operation manual for details.
Note: See Figure 2-8 in User Inputs for factory
reserved inputs which are not user selectable.
Common Faults
The user can program a single fault comprised of faults
from 3 common fault programs—system, digital, and
analog faults.
Up to 62 user-defined system status events and faults
are available. See Group B on the following pages for
specific descriptions. The NFPA 110 faults are part of
the system fault program and are comprised of
15 individual faults shown on the next page.
The user can select up to 21 user-defined digital status
events and faults designated as D01 to D21. Each of the
21 status events and faults are assignable as
shutdowns or warnings.
The user can select up to 7 user-defined analog status
events and faults designated as A01 to A07. Each of the
7 status events and faults are assignable as shutdowns
or warnings with high or low settings for a total of up to
7 status events and fault functions.
Relay Driver Outputs (RDOs)
Up to 31 RDOs are available using the system, digital,
and analog status events and faults. RDOs provide only
the driver. The contact relays that interface with other
equipment are optional.
Note: Func(tion) Used By (RDO) XX Reassign? error
message appears when the user attempts to
duplicate an existing RDO selection.
Note: Cannot Change NFPA is Enabled. error message
appears when the user attempts to modify RDO
setting defaulted as NFPA 110 requirement.
ANALOG INPUTS →
DEFINE COMMON →
FAULTS
Press down arrow to scroll
through RDO’s 1--31 or enter
RDO number.
SYSTEM EVENTS →
COMMON FAULT Y/N
(see Group B)
Press down arrow to scroll
through available faults.
DIGITAL INPUTS →
COMMON FAULT Y/N
(see Group C)
Press down arrow to scroll
through digital auxiliary
inputs.
Menu 10 Overview
ANALOG INPUTS →
COMMON FAULT Y/N
(see Group D)LO WARNING→
Press down arrow to scroll
through analog auxiliary
inputs.
COMMON FAULT Y/N
HI WARNING
→
RELAY DRV OUT XX →
(see Group E)
MENU 10
OUTPUT SETUP
SYSTEM EVENTS →
RELAY DRV OUT XX Y/N
(see Group B)
DIGITAL INPUTS →
RELAY DRV OUT XX Y/N
(see Group C)
RELAY DRV OUT XX Y/N
(see Group D)LO WARNING→
Press down arrow to scroll
through available RDO
faults.
Press down arrow to scroll
through RDO digital auxiliary
inputs.
Press down arrow to scroll
through RDO analog
auxiliary inputs.
RELAY DRV OUT Y/N
HI WARNING
→
COMMON FAULT Y/N
LO SHUTDOWN
→
COMMON FAULT Y/N
HI SHUTDOWN
→
RELAY DRV OUT Y/N
LO SHUTDOWN
→
RELAY DRV OUT Y/N
HI SHUTDOWN
→