TP-6200 10/12 129Section 2 Operation
Local Programming Mode On
2.8.14 Menu 14—Programming Mode
Menu 14 allows altering controller data either locally
using the keypad or remotely using a PC or other device.
The user must enter a password (access code) to
enable the programming mode.
Local Programming. Local programming is data
alteration using the controller keypad and display.
Remote Programming. Remote programming is data
alteration using devices connected to a communication
port using KBUS or Modbusr including Monitor III
software.
Note: Log into the local programming mode to edit the
programming access code. The factory default
access code is the number 0.
Use Menu 14 to change the access code. Record the
new number and give the access code to authorized
individuals only. Should the controller logic not accept
the access code or if the new code number is lost,
contact your local authorized distributor/dealer for
password information.
The user chooses one of three programming modes:
D Local—using the controller keypad
D Remote—using a PC
D Off—no programming is permitted
Enter Yes to one mode to change the other two choices
to No.
Note: Use the generator set controller to initially set up
remote programming. Remote programming is
not allowed from a PC unless the controller is first
set for remote programming using Menu 14.
Note: After completing the programming always place
the controller back in the Programming Mode Off
position to prevent inadvertent program changes.