TP-6200 10/12132 Section 2 Operation
Local Programming Mode On
Menu 15—Protective Relays, continued
Menu 15 Displays with Key Entries
Key
Entry Display Description
Displays the underfrequency % value. When required, use t he
numeric keys to enter the desired underfrequency % value and press
the Enter key.
PR UNDERFREQUENCY →
?% #HZ
Displays the corrected underfrequency % value.
PR UNDERFREQUENCY →
#% #HZ
Displays the underfrequency time delay. When required, use the
numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY →
?SEC
Displays the corrected underfrequency time delay value.
TIME DELAY →
#SEC
PR UNDERFREQUENCY →
?% #HZ
Returns the user to the underfrequency % value display.
Displays the reverse power % value. When required, use the
numeric keys to enter the desired reverse power % value and press
the Enter key.
PR REVERSE POWER →
?% #KW
Displays the corrected reverse power % value.
PR REVERSE POWER →
#% #KW
Displays the reverse power time delay. When required, use the
numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY →
?SEC
Displays the corrected reverse power time delay value.
TIME DELAY →
#SEC
PR REVERSE POWER →
?% #KW
Returns the user to the reverse power % value display.
Displays the reverse power shutdown % value. When required, use
the numeric keys to enter the desired reverse power shutdown %
value and press the Enter key.
SD REVERSE POWER →
?% #KW
Displays the corrected reverse power shutdown % value.
SD REVERSE POWER →
#% #KW
Displays the reverse power shutdown time delay. When required,
use the numeric keys to enter the desired time delay value and press
the Enter key.
TIME DELAY →
?SEC
Displays the corrected reverse power shutdown time delay value.
TIME DELAY →
#SEC
SD REVERSE POWER →
?% #KW
Returns the user to the reverse power shutdown % value display.
Displays the over power % value. When required, use the numeric
keys to enter the desired over power % value and press the Enter
key.
PR OVER POWER →
?% #KW
Displays the corrected over power % value.
PR OVER POWER →
#% #KW
Displays the over power time delay. When required, use the numeric
keys to enter the desired time delay value and press the Enter key.
TIME DELAY →
?SEC
Displays the corrected over power time delay value.
TIME DELAY →
#SEC
PR OVER POWER →
?% #KW
Returns the user to the over power % value display.