Kohler 20-3250 kW Portable Generator User Manual


 
TP-6200 10/12132 Section 2 Operation
Local Programming Mode On
Menu 15—Protective Relays, continued
Menu 15 Displays with Key Entries
Key
Entry Display Description
Displays the underfrequency % value. When required, use t he
numeric keys to enter the desired underfrequency % value and press
the Enter key.
PR UNDERFREQUENCY
?% #HZ
Displays the corrected underfrequency % value.
PR UNDERFREQUENCY
#% #HZ
Displays the underfrequency time delay. When required, use the
numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY
?SEC
Displays the corrected underfrequency time delay value.
TIME DELAY
#SEC
PR UNDERFREQUENCY
?% #HZ
Returns the user to the underfrequency % value display.
Displays the reverse power % value. When required, use the
numeric keys to enter the desired reverse power % value and press
the Enter key.
PR REVERSE POWER
?% #KW
Displays the corrected reverse power % value.
PR REVERSE POWER
#% #KW
Displays the reverse power time delay. When required, use the
numeric keys to enter the desired time delay value and press the
Enter key.
TIME DELAY
?SEC
Displays the corrected reverse power time delay value.
TIME DELAY
#SEC
PR REVERSE POWER
?% #KW
Returns the user to the reverse power % value display.
Displays the reverse power shutdown % value. When required, use
the numeric keys to enter the desired reverse power shutdown %
value and press the Enter key.
SD REVERSE POWER
?% #KW
Displays the corrected reverse power shutdown % value.
SD REVERSE POWER
#% #KW
Displays the reverse power shutdown time delay. When required,
use the numeric keys to enter the desired time delay value and press
the Enter key.
TIME DELAY
?SEC
Displays the corrected reverse power shutdown time delay value.
TIME DELAY
#SEC
SD REVERSE POWER
?% #KW
Returns the user to the reverse power shutdown % value display.
Displays the over power % value. When required, use the numeric
keys to enter the desired over power % value and press the Enter
key.
PR OVER POWER
?% #KW
Displays the corrected over power % value.
PR OVER POWER
#% #KW
Displays the over power time delay. When required, use the numeric
keys to enter the desired time delay value and press the Enter key.
TIME DELAY
?SEC
Displays the corrected over power time delay value.
TIME DELAY
#SEC
PR OVER POWER
?% #KW
Returns the user to the over power % value display.