TP-6200 10/12 117Section 2 Operation
Local Programming Mode On
Menu 11—Voltage Regulator, continued
Menu 11 Displays with Key Entries
Key
Entry Display Description
REACTIVE DROOP →
ENABLED N/Y
Returns the user to reactive droop selection heading.
VAR CONTROL →
ENABLED N/Y
Displays the VAR control selection (yes or no).
Press the Enter key.
Confirms the entry.
VAR CONTROL →
ENABLED YES
VAR CONTROL →
ENABLED YES
Entering YES enables the VAR control feature.
Note: A YES entry disables the PF control if previously activated.
VAR CONTROL →
ENABLED NO
OR
Confirms the entry.
Press the Enter key.
VAR CONTROL →
ENABLED NO
VAR CONTROL →
ENABLED NO
Entering NO disables the VAR control feature.
VAR CONTROL →
ENABLED YES
TOTAL KVAR #→
KVAR ADJ ?.?
Displays total kVAR (running) and kVAR adjustment settings. Enter
the desired kVAR adjustment using the numeric keys. Press the
Menu Right
→ key prior to entering the decimal value.
Confirms the entry.
TOTAL KVAR #→
KVAR ADJ #.#
AND
Use the numeric keys to enter the decimal value. Press the Enter
key.
TOTAL KVAR #→
KVAR ADJ ?.?
GENERATING/ N/Y→
ABSORBING
Displays the generating or absorbing kVAR selection.
Note: The display sample may differ depending upon the previous
entries. The generating selection is the factory default setting.
Displays the generating kVAR selection. When required, use the NO
key to choose absorbing kVAR.
Confirms the entry.
GENERATING YES→
ABSORBING YES→
Press the Enter key.
GENERATING NO→
ABSORBING YES→
OR
Confirms the entry.
ABSORBING NO→
GENERATING YES→
Displays the absorbing kVAR selection. When required, use the NO
key to choose generating kVAR.
Press the Enter key.
VAR CONTROL →
ENABLED N/Y
Returns the user to VAR control selection heading.