TP-6200 10/12 103Section 2 Operation
Local Programming Mode On
Menu 9—Input Setup, continued
Menu 9 Displays with Key Entries
Key
Entry Display Description
Displays the analog input 01, high shutdown value. When required,
use the numeric keys to set the new values. Press the Enter key.
Note: The user must scale the analog input value in order to calculate
the low/high warning and shutdown values based on a 0--5 VDC
scale. See Menu 12—Calibration.
ANALOG INPUT 01 →
HI SDWN VALUE ?
Displays the corrected high shutdown value.
ANALOG INPUT 01 →
HI SDWN VALUE #
ANALOG INPUT 01 →
(USER DEFINED DESC)
Returns the user to analog input 01.
ANALOG INPUT XX →
(USER DEFINED DESC)
Displays analog inputs A02 to A07. Note: Press the down arrow to
scroll through additional analog auxiliary inputs or enter the i nput
number. Note: ECM engines have inputs A01--A07 and non-ECM
engines have inputs A03--A07. Waukesha engines have inputs
A05--A07.
Note: Press the right arrow at each analog auxiliary input for the
following selections and settings:
Warning enabled
Shutdown enabled
Inhibit time
Warning delay time
Shutdown delay time
Low shutdown value
Low warning value
High warning value
High shutdown value
See the Analog Input 01 instructions for the complete procedure.
SETUP DIGITAL →
AUXILIARY INPUTS
Returns the user to the setup analog auxiliary input heading.
SETUP ANALOG →
AUXILIARY INPUTS
Returns the user to the setup digital auxiliary input heading.
ANALOG INPUT 01 →
HI WARN VALUE ?
Displays the analog input 01, high warning value. When required,
use the numeric keys to set the new values. Press the Enter key.
Note: The user must scale the analog input value in order to calculate
the low/high warning and shutdown values based on a 0--5 VDC
scale. See Menu 12—Calibration.
Displays the corrected high warning value.
ANALOG INPUT 01 →
HI WARN VALUE #