TP-6200 10/12 121Section 2 Operation
Local Programming Mode On
Menu 12—Calibration, continued
Menu 12 Displays with Key Entries (Scale AC Analog Inputs)
Key
Entry Display Description
GEN L2-L0 V #
CALIB REF ?.?
Measure the generator set output voltage for three-phase models
between L2-L0 using a voltmeter and enter the result using the
numeric keys. Press the Menu Right
→ key prior to entering the
decimal value.
Confirms the entry.
GEN L2-L0 V #
CALIB REF #.#
AND
Use the numeric keys to enter the decimal value. Press the Enter
key.
GEN L2-L0 V #
CALIB REF ?.?
GEN L3-L0 V #
CALIB REF ?.?
Three-Phase Models only. Measure the generator set output
voltage for three-phase models between L3-L0 using a voltmeter and
enter the result using the numeric keys. Press the Menu Right
→ key
prior to entering the decimal value.
Confirms the entry.
GEN L3-L0 V #
CALIB REF #
AND
Use the numeric keys to enter the decimal value. Press the Enter
key.
GEN L3-L0 V #
CALIB REF ?.?
GEN VOLTAGE LN
Returns the user to the generator set voltage line-to-neutral heading.
Displays the generator set voltage line-to-line heading.
GEN VOLTAGE LL
GEN L1-L2 V #
CALIB REF ?.?
Note: The generator set must be running for the following steps.
Measure the generator set output voltage for single and three-phase
models between L1-L2 using a voltmeter and enter the result using
the numeric keys. Press the Menu Right → key prior to entering the
decimal value.
Confirms the entry.
GEN L1-L2 V #
CALIB REF #.#
AND
Use the numeric keys to enter the decimal value. Press the Enter
key.
GEN L1-L2 V #
CALIB REF ?.?
GEN L2-L3 V #
CALIB REF ?.?
Three-Phase Models only. Measure the generator set output
voltage for three-phase models between L2-L3 using a voltmeter and
enter the result using the numeric keys. Press the Menu Right
→ key
prior to entering the decimal value.
Note: The generator set must be running for the following steps.
Confirms the entry.
GEN L2-L3 V #
CALIB REF #.#
AND
Use the numeric keys to enter the decimal value. Press the Enter
key.
GEN L2-L3 V #
CALIB REF ?.?