TP-6200 10/12 27Section 1 Specifications and Features
Factory-Defined Settings
Status Event
or Fault
Time
Delay
(sec.)
Inhibit
Time
Delay
(sec.)
Default
Selection
Range SettingLamp
Alarm
Horn
Relay
Driver
Output
(RDO)
Digital Display
Refer
to
Menu
Fuel Level (see A04)
Fuel Valve Relay ]
10 FUEL VALVE
RELAY
RDO-23 ]
Generator Set
Running
10 RDO-15
(lead 70R)
Off
Ground Fault
Detected
10 GROUND
FAULT
On Warning
High Battery Voltage 10 HIGH
BATTERY
VOLTAGE
RDO-13 Off Warning 14.5--16.5 V (12 V)
29--33 V (24 V)
16 V (12 V)
32 V (24 V)
10
High Coolant
Temperature
Shutdown
10 HI COOL
TEMP
SHUTDOWN
RDO-03
(lead 36)
On Shutdown 30 5
High Coolant
Temperature Warning
10 HI COOL
TEMP
WARNING
RDO-06
(lead 40)
On Warning 30
High Oil Temperature
Shutdown
10 HI OIL TEMP
SHUTDOWN
On Shutdown 30 5
High Oil Temperature
Warning ][[
10 HI OIL TEMP
WARNING
On Warning 30
Idle (speed) Mode
Function (see D21)
In Synch w
10 IN SYNCH RDO-29 *
Intake Air
Temperature
Shutdown [[
10 INTAKE AIR
TEMP SDWN
On Shutdown 30
Intake Air
Temperature Warning
[[
10 INTAKE AIR
TEMP WARN
On Warning 30
Intake Air Temp
Warning(seeA03)]
Intake Air Temp
Shutdown (see
A03)]
Internal Fault
Shutdown
10 INTERNAL
FAULT
On Shutdown
J1939 CAN
Shutdown (see
Engine J1939 CAN
Shutdown)
Knock Shutdown
(see D13) ]
kW Overload
(see Load Shed)
Load Shed
kW Overload ]]
10 LOAD SHED
KW OVER
RDO-30 ]]
Off Warning 80%--120% 100% of
kW rating
with5sec.
delay
2--10
Load Shed Over
Temperature [[
(Activated by a High
Coolant Temp.
shutdown)
10 LOAD SHED
OVER
TEMPERATURE
RDO only
Load Shed
Underfrequency [
10 LOAD SHED
UNDER
FREQUENCY
RDO-31 [
Off Warning 59 Hz
(60 Hz)
49 Hz
(50 Hz)
5
* All models, except Waukesha-powered models. ** NFPA applications
[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC
] Waukesha-powered models ]] FAA only
w Paralleling applications