TP-6200 10/12 187Section 6 Accessories
TB1 Terminal Strip—Engine Start and
Emergency Stop Connections
Term. Description
1 Emergency stop ground
1A Emergency stop
3 Remote start
4 Remote start
TB2 Terminal Strip—Analog Input Connections
Term. Description
1 ACH1 (CTS) Signal (non-ECM including Waukesha)
2 ACH1 (CTS) Supply (non-ECM including Waukesha)
3 ACH2 (OPS) Signal (non-ECM including Waukesha)
4 ACH2 (OPS) Supply (non-ECM including Waukesha
5 ACH3 Signal (air intake temp. for Waukesha)
6 ACH3 Supply (air intake temp. for Waukesha)
7 ACH4 Signal (oil temp. for Waukesha)
8 ACH4 Supply (oil temp. for Waukesha)
9 ACH5 Signal
10 ACH5 Supply
11 ACH6 Signal
12 ACH6 Supply (VSG for Volvo, GM, Doosan)
13 ACH7 Signal (optional analog voltage adjust signal)
14 ACH7 Supply
15 N/C
16 ACH1 (CTS) Return (non-ECM)
17 ACH1 (CTS) Shield ground (non-ECM)
18 ACH2 (OPS or OPS2) Return (non-ECM)
19 ACH2 (OPS) Shield ground (non-ECM)
20 ACH3 (IAT or OPS1) Return
21 ACH3 Shield ground
22 ACH4 (Oil Temp) Return
23 ACH4 Shield ground
24 ACH5 Return
25 ACH5 Shield ground
26 ACH6 Return
27 ACH6 Shield ground
28 ACH7 Return
29 ACH7 Shield ground
30 N/C
TB3 Terminal Strip—Accessory Power Output
Connections
Term. Description
1 +12 VDC (OEM use only)
2 +12 VDC (OEM use only)
3 +12 VDC (OEM use only)
4 Fused battery (+) (42A) (5 amp)
5 Fused battery (+) (42A) (5 amp)
6 Fused battery (+) (42A) (5 amp)
7 Battery (--)
8 Battery (--)
9 Battery (--)
10 Battery (--)
11 Battery (--)
12 Panel lamp output
TB4 Terminal Strip—Input Factory Connections
Term. Description
1 DCH1 Battery charger fault
2 DCH2 Low fuel
3 DCH3 Low coolant temp. with ECM models or
warning default with non-ECM models
4 DCH4 Field overvoltage with M4/M5/M7
alternators or warning default with
non-M4/M5/M7 alternators
5 DCH5 Breaker Closed, Paralleling Applications
6 DCH6 Enable Synch, Paralleling Applications
7 DCH7 Warning
8 DCH8 Warning
9 DCH9 Warning
10 DCH10 Warning
11 DCH11 AFM Shutdown, Waukesha engine
12 DCH12 Detonation Warning, Waukesha engine
13 DCH13 Detonation Shutdown,
Waukesha engine
14 DCH14 Warning
15 DCH15 Remote shutdown
16 DCH16 Remote reset
17 DCH17 VAR PF mode
18 DCH18 Voltage lower
19 DCH19 Voltage raise
20 DCH20 Air damper
21 DCH21 Idle mode functional with
ECM-equipped engines only
22 DCH1 Return
23 DCH2 Return
24 DCH3 Return
25 DCH4 Return
26 DCH5 Return
27 DCH6 Return
28 DCH7 Return
29 DCH8 Return
30 DCH9 Return
31 DCH10 Return
32 DCH11 Return
33 DCH12 Return
34 DCH13 Return
35 DCH14 Return
36 DCH15 Return
37 DCH16 Return
38 DCH17 Return
39 DCH18 Return
40 DCH19 Return
41 DCH20 Return
42 DCH21 Return
Note: TB4-1 through TB4-21 are user definable with
factory defaults listed. Terminals TB4-3, TB4-4,
TB4-14, and TB4-21 have different functions
depending upon the generator set configuration.
See comments above.
See Menu 9—Input Setup for changing inputs.
Figure 6-38 Controller Terminal Strip Identification