TP-6200 10/12 87Section 2 Operation
Local Programming Mode On
Menu 4—Operational Records, continued
Menu 4 Displays with Key Entries
Key
Entry Display Description
Press the Enter key.
Confirms the entry. The generator set will begin cranking and run
based on the run time (hours:minutes) period and all previously
established time (hours:minutes) delays from Menu 8—Time Delays.
Note: Press the STOP PROG RUN key to stop the generator set
when in the run time mode, if necessary.
ENGINE START? YES
COUNTDOWN ##:##
RUN TIME HR:MN
##:##
RUN TIME SINCE MAINT
UNLOADED HRS #
Displays the run time since the last maintenance with unloaded
hours.
RUN TIME SINCE MAINT
KW HRS #
Displays the run time since the last maintenance in kW hours.
OPERATING DAYS #
LAST MAINT ##-###-##
Displays the operating days since the last maintenance.
NO. OF STARTS #
LAST MAINT ##-###-##
LAST START ##:## AM/PM
DATE ##-###-##
LENGTH OF RUN
(UN)LOADED HRS #
Displays the number of starts since the last maintenance date
(day-month-year).
Displays last the start time (hours:minutes) and date
(day-month-year).
Displays the length of last run in (un)loaded hours.
MENU 4
OPERATIONAL RECORDS
Returns the user to the operational records heading.
RECORDS MAINT
Displays the records maintenance subheading.
Displays the run time since the last maintenance with total hours.
RUN TIME SINCE MAINT
TOTAL HRS #
RECORDS MAINT
Returns the user to records maintenance subheading.
RESET RECORDS?
Displays the reset records option. After performing maintenance or
when required, enter Yes to reset.
RUN TIME SINCE MAINT
LOADED HRS #
Displays the run time since last the maintenance with loaded hours.
RESET RECORDS? YES
Enter Yes to reset to the current date and press the Enter key.
RESET RECORDS? YES
Confirms the entry.