TP-6200 10/12200 Appendix
Status Event
or Fault
User-Defined
Settings
Time
Delay
(sec.)
Inhibit
Time
Delay
(sec.)
Default
Selection
Range Setting
Relay
Driver
Output
(RDO)
Digital Display
Refer
to
Menu
No Coolant
Temperature Signal
10 NO COOL
TEMP SIGNAL
30 4 Not adjustable
No Oil Pressure
Signal
10 NO OIL
PRESSURE
SIGNAL
30 4 Not adjustable
No Oil Temperature
Signal Warning ]
10 NO OIL TEMP
SIGNAL
30 4 Not adjustable
Overcrank Shutdown 8, 10 OVER CRANK RDO-02
(lead 12)
0--6 Cycles 3 Cycles
Overcurrent 10 OVER
CURRENT
110% 10 Not adjustable
Over Current VR
(voltage restraint)
Shutdownw
10 SD OVER
CURRENT VR
Not adjustable
Overfrequency
Shutdown
7, 10 OVER
FREQUENCY
RDO-28 102%--140% 110% Std.
103% FAA
10
Over Power
Shutdown w
10 SD OVER
POWER
102%
Stdby
112% Prime
Not adjustable
Overspeed
Shutdown
7, 10 OVER SPEED RDO-01
(lead 39)
65--70 Hz (60 Hz)
55--70 Hz (50 Hz)
70 (60 Hz)
70 (50 Hz)
0.25
Overvoltage
Shutdown
7, 8,
10
OVER
VOLTAGE
RDO-20
(lead 26)
105%--135%
of nominal
115%
2-sec time
delay[
135%
10-sec time
delayw
2--10
Password
(see Access Code)
—
Pre Lube Relay ]
10 PRE LUBE
RELAY
RDO-26 ]
4 Not adjustable
Remote Reset
(see D16)
—
Remote Shutdown
(see D15)
—
Reverse Power
Shutdown w
10 SD REVERSE
POWER
Not adjustable
Speed Sensor Fault 10 SPEED
SENSOR
FAULT
RDO-24 Not adjustable
Starting Aid (see
Time Delay Starting
Aid)
—
System Ready 10 RDO-17
(lead 60)
Not adjustable
Time Delay Engine
Cooldown (TDEC)
8, 10 DELAY ENG
COOLDOWN
RDO-16
(lead 70C)
00:00--10:00
min:sec
5:00
Time Delay Engine
Start (TDES)
8, 10 DELAY ENG
START
00:00--5:00
min:sec
00:01
Time Delay Starting
Aid
8, 10 0--10 sec.
Underfrequency 7, 10 UNDER
FREQUENCY
RDO-29 ]
80%--97% 97% FAA
90%[
80%w
10
* All models, except Waukesha-powered models. ** NFPA applications
[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC
] Waukesha-powered models ]] FAA only
w Paralleling applications