TP-6200 10/12124 Section 2 Operation
Local Programming Mode On
Menu 12—Calibration, continued
Menu 12 Displays with Key Entries (Scale Aux. Analog Inputs)
No calibration is available for inputs A01--A02 for
non-ECM engines. No calibration is available for inputs
A01--A04 for Waukesha engines.
Key
Entry Display Description
Input a menu number.
MENU 12
CALIBRATION
SCALE AC ANALOG
INPUTS
Displays the scale AC analog inputs heading.
MAIN MENU NUMBER 12
ENTER MENU NO. 1--15
Press the Enter key.
Displays the menu number and name.
Displays the scale auxiliary analog inputs heading.
SCALE AUX. ANALOG →
INPUTS
ZERO AUX. ANALOG
INPUTS?
Gives the user the option to calibrate the auxiliary analog inputs for
zero input signals. Note: ECM engines have inputs A01--A07 and
non-ECM engines have inputs A03--A07. A07 may be used for
analog voltage adjust. Waukesha engines have inputs A05-- A07.
When required, enter YES to activate the auto-zero auxiliary analog
inputs feature. Press the Enter key.
Confirms the entry.
ZERO AUX. ANALOG
INPUTS? YES
ZERO AUX. ANALOG
INPUTS? YES
ANALOG 01 #
SCALE VALUE 1 ?
Displays the analog 01 and scale value 1 settings. Use the numeric
keys to enter the minimum value based on the previously calculated
5 VDC analog input value.
SCAL 1 #--#.#V
SCAL 2 #--#.#V
Note: Press the Menu Right → key to review both the scale value 1
and scale value 2 settings any time during the setup procedure.
ANALOG 01 #
SCALE VALUE 2 ?
Displays analog 01 and scale value 2 settings. Use the numeric keys
to enter the maximum value based on the previously calculated
5 VDC analog value.
Returns the user to the scale auxiliary analog inputs heading.
SCALE AUX. ANALOG →
INPUTS
ANALOG XX #
SCALE VALUE 1 ?
Displays scale auxiliary analog inputs 01 to 07.
Note: Press the down arrow to scroll through the additional analog
auxiliary inputs 02--07.
Note: Press the down arrow to scroll through the additional analog
scale value 1 and value 2 for each analog selection.
Note: Press the right arrow at each analog auxiliary input that
provides display of the scale 1 and scale 2 voltage settings.
ZERO AUX. ANALOG
INPUTS?
Press the down arrow to go to the desired analog XX.