Kohler 20-3250 kW Portable Generator User Manual


 
TP-6200 10/12110 Section 2 Operation
Local Programming Mode On
Menu 10—Output Setup, continued
Menu 10 Displays with Key Entries
Entering YES adds the selection to the RDO group.
Note: Func(Function) Used by (RDO) XX Reassign? appears when
the user attempts to assign an RDO to a function already assigned.
Note: Cannot Change (because the) NFPA is Enabled appears when
the user attempts to modify the RDO setting that is a NFPA 110
default requirement.
Key
Entry Display Description
DIGITAL INPUTS
Displays the digital inputs heading.
Gives the user the option to assign a digital input to an RDO starting
with D01. Press the Menu Down key to continue to the next selection
D02--D21 (repeat as necessary).
Note: Func(Function) Used by (RDO) XX Reassign? appears when
the user attempts to assign an RDO to a function already assigned.
Press the Enter key.
Confirms the entry.
RELAY DRV OUT 01 Y/N
Dxx (see Group C)
RELAY DRV OUT 01 YES
Dxx (see Group C)
RELAY DRV OUT 01 YES
Dxx (see Group C)
ANALOG INPUTS
Displays the analog inputs heading.
RELAY DRV OUT 01 NO
Dxx (see Group C)
Gives the user the option to assign an analog input to an RDO
starting with A01. Note: Press the Menu Down key to continue to the
next selection A02-A07 (repeat as necessary).
Group C
Up to user-defined digital status
and fault inputs designated as
D01 to D21 can result in a digital
input common fault.
Group D
Up to 7 analog inputs, user-
defined status events and
faults designated as A01 to
A07. Each of the 7 is
assignable as a shutdown or
warning with high or low
settings.
RELAY DRV OUT 01 Y/N
Axx
(see Group D) LO
WARNING