TP-6200 10/1224 Section 1 Specifications and Features
Factory-Defined Settings
Status Event
or Fault
Refer
to
Menu
Digital Display
Relay
Driver
Output
(RDO)
Alarm
Horn
Lamp Range Setting
Default
Selection
Inhibit
Time
Delay
(sec.)
Time
Delay
(sec.)
Access Code
(password)
14 User-Selectable 0(zero)
AC Sensing Loss 10 AC SENSING
LOSS
RDO-25 * On Warning
Air Damper Control
(if used) **
10
Air Damper Indicator
(if used), see D20 **
Air/Fuel Module
(AFM) Engine Start
Delay ]
10 AFM ENG
START DELAY
Fixed
Air/Fuel Module
(AFM) Remote
Start]
10 AFM REMOTE
START
RDO-25 ]
Off
Air/Fuel Module
(AFM) Shutdown
(see D11) ]
Alternator Protection
Shutdown
10 ALTERNATOR
PROTECTION
On Shutdown
Analog Aux. Input 0 9 LOCAL BATT
VDC
Fixed
Analog Aux. Inputs
A01--A07
9 USER-DEFINED
A01--A07
On Shutdown
or
Warning
Default Values with
Warning Enabled:
HI warning 90%
LO warning 10%
HI shutdown 100%
LO shutdown 1%
30 sec.
inhibit,
5 sec. delay
0--60 0--60
Analog Aux. Input
A01 (non-ECM only)
9 A01
COOLANT
TEMP
On Shutdown
or
Warning
Default Values with
Warning Enabled:
HI/LO warning and
HI/LO shutdown are
all engine dependent
30 sec.
inhibit,
0 sec. delay
warning,
5 sec. delay
shutdown
Analog Aux. Input
A02 (non-ECM only)
9 A02
OIL
PRESSURE
On Shutdown
or
Warning
Default Values with
Warning Enabled:
HI/LO warning and
HI/LO shutdown are
all engine dependent
(255 psi max.)
30 sec.
inhibit,
0 sec. delay
warning,
5 sec. delay
shutdown
Analog Aux. Input
A03 ]
9 A03
INTAKE AIR
TEMP
Shutdown
or
Warning
Default Values with
Warning Enabled:
HI/LO warning and
HI/LO shutdown are
all engine dependent
30 sec.
inhibit,
0 sec. delay
warning
Analog Aux. Input
A04 *
9 A04
FUEL LEVEL
Default Values with
Warning Enabled:
HI/LO warning are
engine dependent
30 sec.
inhibit,
0 sec. delay
warning
Analog Aux. Input
A04 ]
9 A04
OIL TEMP
On Warning Default Values with
Warning Enabled:
HI/LO warning are
engine dependent
30 sec.
inhibit,
0 sec. delay
warning
Analog Aux. Input
A06 VSG (Volvo,
GM, Doosan only)
9, 12 A06 ANALOG
AUXILIARY IN
Off Volvo:
0.5V=1250
4.5V=8750
GM/Doosan
60 Hz:
0.5V=2375
4.5V=2625
50 Hz:
0.5V=2327
4.5V=2624
* All models, except Waukesha-powered models. ** NFPA applications
[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC
] Waukesha-powered models ]] FAA only
w Paralleling applications