Kohler 20-3250 kW Portable Generator User Manual


 
TP-6200 10/12 53Section 2 Operation
2.7.1 Menu 1—Generator Monitoring
Menu 1 displays generator output data including
line-to-line and line-to-neutral voltages, current,
frequency, power factor, total kilowatts, percent of
maximum kW, total kVA , and total kVAR. Menu 1
displays three-phase voltage and current readings
when applicable.
All menu displays apply to both single-phase and three-
phase voltages unless otherwise noted as (1 PH) or
(3 PH) on the menu overview. The phase designation
does not appear in the controller menu displays.
Note: For the auto-scroll function, press ENTER at V &
A Summary menu. Press the Reset Menu key or
Menu Right key to stop the auto-scroll function.
Note: Pressing a right arrow key from any submenu
moves to the next submenu header.
VOLTS&AMPS
L1-L2 VOLTS #
L1 AMPS #
L2-L3 VOLTS #
L2 AMPS #
L1-L0 VOLTS #
L1 AMPS #
L2-L0 VOLTS #
L2 AMPS #
L3-L0 VOLTS #
L3 AMPS #
FREQUENCY # HZ
V&ASUMMARY
V L1-L2 L2-L3 L3-L1
###
V L1-L0 L2-L0 L3-L0
###
A L1L2L3
###
For the auto-scroll function,
press ENTER at
V&ASUMMARY menu.
POWER KW
TOTAL KW #
PF # LEADING/LAGGING
L1 KW #
PF # LEADING/LAGGING
Menu 1 Overview (Three-Phase Connections)
POWER KVAR
TOTAL KVAR #
ABSORBING/GENERATING
L1 KVAR #
ABSORBING/GENERATING
L2 KVAR #
ABSORBING/GENERATING
L3 KVAR (3 PH) #
ABSORBING/GENERATING
POWER KVA
TOTAL KVA #
L1 KVA #
L2 KVA #L2 KW #
PF # LEADING/LAGGING
L3 KW (3 PH) #
PF # LEADING/LAGGING
TOTAL KW #
% OF RATED KW #
L3 KVA #
L3-L1 VOLTS #
L3 AMPS #
MENU 1
GENERATOR MONITORING
Use the MENU key to