Kohler 20-3250 kW Portable Generator User Manual


 
TP-6200 10/12102 Section 2 Operation
Local Programming Mode On
Menu 9—Input Setup, continued
Menu 9 Displays with Key Entries
ANALOG INPUT 01
SHUTDOWN ENABLED NO
Key
Entry Display Description
ANALOG INPUT 01
SHUTDOWN ENABLED Y/N
Displays the analog input 01, shutdown enabled selection.
Press the Enter key.
AND
Confirms the entry.
OR
Press the Enter key.
AND
Confirms the entry.
ANALOG INPUT 01
SHUTDOWN ENABLED YES
ANALOG INPUT 01
SHUTDOWN ENABLED YES
ANALOG INPUT 01
SHUTDOWN ENABLED NO
Displays the corrected low warning value.
ANALOG INPUT 01
SDWN DELAY TIME ?:??
Displays the analog input 01, shutdown time (minutes:seconds) delay
setting. When required, use the numeric keys to set the new values.
Press the Enter key.
ANALOG INPUT 01
LO WARN VALUE ?
Displays the analog input 01, low warning value. When required, use
the numeric keys to set the new values. Press the Enter key.
Note: The user must scale the analog input value in order to calculate
the low/high warning and shutdown values based on a 0--5 VDC
scale. See Menu 12—Calibration.
ANALOG INPUT 01
INHIBIT TIME ?:??
Displays the analog input 01, inhibit time (minutes:seconds) setting.
When required, use the numeric keys to set the new values. Press
the Enter key.
ANALOG INPUT 01
WARN DELAY TIME ?:??
Displays the analog input 01, warning time (minutes:seconds) delay
setting. When required, use the numeric keys to set the new values.
Press the Enter key.
ANALOG INPUT 01
INHIBIT TIME #:##
Displays the corrected inhibit time (minutes:seconds) setting.
Displays the corrected warning time (minutes:seconds) delay setting.
ANALOG INPUT 01
WARN DELAY TIME #:##
Displays the corrected shutdown time (minutes:seconds) delay
setting.
ANALOG INPUT 01
SDWN DELAY TIME #:##
ANALOG INPUT 01
LO WARN VALUE #
Entering YES enables the shutdown analog input 01.
ANALOG INPUT 01
SHUTDOWN ENABLED NO
Entering NO disables the shutdown analog input 01.
ANALOG INPUT 01
SHUTDOWN ENABLED YES
Displays the analog input 01, low shutdown value. When required,
use the numeric keys to set the new values. Press the Enter key.
Note: The user must scale the analog input value in order to calculate
the low/high warning and shutdown values based on a 0--5 VDC
scale. See Menu 12—Calibration.
ANALOG INPUT 01
LO SDWN VALUE ?
Displays the corrected low shutdown value.
ANALOG INPUT 01
LO SDWN VALUE #