FRONT ENGINE ACCESS
SAFETY:
1. Set the AUTO-OFF-MANUAL switch to OFF.
2. Remove the 7.5 amp main fuse. See Figure 1.
3. Remove the N1 and N2 fuse from the transfer switch.
Figure 1. Remove 7.5 Amp Fuse
4. Turn off fuel supply to the generator and remove the flex-
line from the fuel regulator.
5. Remove utility power from the generator.
6. Remove front door.
7. Remove battery from the generator.
FRONT ENGINE ACCESS:
1. Remove Controls Cover: Using a Torx T-27 socket
remove two bolts and ground washer from the controls
cover. Remove the controls cover. See Figure 2.
Figure 2.
2. Remove controller: Using a Phillips screwdriver remove the
four mounting screws from the controller. See Figure 3.
Figure 3.
3. Remove control harnesses:
a. Remove engine wiring harness at the J1 port.
b. Remove control wiring harness at the J2 port.
c. Remove stepper motor wiring harness at the J3
port. See Figure 4.
Figure 4.
PART 6
DISASSEMBLY
SECTION 6.1
MAJOR DISASSEMBLY
Page 152