Sun Microsystems 3900 Outdoor Storage User Manual


 
Appendix A Virtualization Engine References 157
Sun Proprietary/Confidential: Internal Use Only
70021 The drive is offline. If the change was unintentional, check the
condition of the drives.
70022 The virtualization engine is offline. If the change was unintentional, check the
condition of the drives.
70023 The drive is unresponsive. Check the condition of drives.
70024 For the Sun StorEdge T3+ array pack, the master
virtualization engine has detected the partner
virtualization engine’s IP Address.
No action is needed.
70025 For Sun StorEdge T3+ array pack: The master
virtualization engine is unable to detect the
partner virtualization engine’s IP address.
Check the Ethernet connection between
the two virtualization engines.
70030 The SAN configuration was changed by theSAN
Builder.
No action is needed.
70040 The zoning configuration of the host has
changed.
No action is needed.
70050 A multipath drive failover occurred. Check the multipath drive.
70051 A multipath drive failback occurred. No action is needed.
70098 Instant copy degraded. If no spare is available, replace the failed
drive with a new drive.
70099 Degrade because the drive has disappeared. Reinsert the missing drive, or replace it
with a drive of equal or greater capacity.
7009A A mirror drive was written to, causing it to enter
the read degrade state.
Reinsert the missing drive, or replace it
with a drive of equal or greater capacity.
7009B A drive entered the write degrade state. Reinsert the drive (if good) or replace it if
it is defective.
7009C During a rebuild, the last primary drive failed.
This is a very rare multipoint failure.
1. Backup the drive data.
2. Destroy the mirror drive where the
failure has occurred.
3. Format the drives using mode 14.
4. Create a new mirror drive.
5. Reassign the old SCSI ID and LUN to
the new mirror drive.
6. Restore the data.
71000 Communication has been recovered between the
two virtualization engines.
No action is needed.
TABLE A-1 SRN Reference
SRN Description Corrective Action