Sun Microsystems 3900 Outdoor Storage User Manual


 
82 Sun StorEdge 3900 and 6900 Series 2.0 Troubleshooting Guide March 2003
Sun Proprietary/Confidential: Internal Use Only
TABLE 7-2 lists the switch events for Sun StorEdge network FC switch-8 and switch-
16 2 Gbit switches.
TABLE 7-2 Storage Automated Diagnostic Environment Event Grid for 2 GBit Switches
Component
EventType
Severity
Action
Description
Note:
Text within
quotation marks
(“ “) is exactly
as it appears on
the Event Grid.
Action
Required
chassis.
fan
Alarm- Yellow Y “chassis.fan.1 status
changed from OK”
None.
chassis.
board
Alarm- Yellow Y The uptime of the switch
was less than the previous
uptime of the switch. This
could indicate that the
switch has been reset either
by a user or by the loss of
power.
1. Check to seeif the switch
has been reset.
2. Check the power going
to the switch.
chassis.
power
Alarm Yellow “chassis.power.1 status
changed from OK”
This event monitors
changes in the status of the
chassis’ power supply, as
reported by the SANbox
chassis status.
None.
system_
reboot
Alarm Yellow “Switch sw1a was rezoned”
This event reports changes
in the zoning of a switch.
enclosure Audit “Auditing a new switch
called ras d2-swb1
(ip=xxx.0.0.41)
10002000007a609”
oob Comm_
Established
“Communication regained
with
sw1a
(ip=xxx.20.67.213)”