Hydrastep 2468CB and 2468CD Manual Delay Relay Output Board Option
24685034
3b-15
3b.3.2.6 ‘Two out of Four’ Relay Alarm System (contd.)
In the following diagrams (6A & 6B)
indicate the electrode channel selected for
each relay. A fully functioning system (NO FAULTS) will perform a low level trip at electrode
level 2. For a high level trip, using electrode channels 9, 10, 11 and 12 respectively and
switch SW5 set for ES, a healthy system would trip at level 11.
Case A - Relays normally energised, de-energise one in each pair to trip
(Relays shown in de-energised state)
1
4
3
2
5
8
7
6
(Switch SW5 is set to EW for low-level alarms and set to ES for high-level alarms)
1
4
3
2
5
8
7
6
To alarm
annunciator
or tripping
device
RL 1
RL 2
RL 2
RL 1
PL 2
PL 2
Odd electrodes
(RH input board)
Even electrodes
(LH input board)
3
1
4
2
Alarm off when contacts closed
Case B - Relays normally de-energised, energise one in each pair to trip
(Relays shown in de-energised state)
1
4
3
2
5
8
7
6
(Switch SW5 is set to EW for low-level alarms and set to ES for high-level alarms)
1
4
3
2
5
8
7
6
To alarm
annunciator
or tripping
device
RL 1
RL 2
RL 2
RL 1
PL 2
PL 2
Odd electrodes
(RH input board)
Even electrodes
(LH input board)
3
1
4
2
Alarm off when contacts open