Black Box MPSH8-D20-120V Multi-tool User Manual


 
OUTLET MANAGED PDU
24
2. Set Parameters to Factory Defaults:
a) Simultaneously press both the Default button and the Reset button, hold
them for ve seconds, and then release them.
b) All Outlet Managed PDU parameters will be reset to their original
factory default settings, and the unit will then reboot. All plugs will be
left in their current On/Off state.
3. Toggle/Default All Plugs:
a) Press the Default button, hold it for ve seconds, and then release the
Default Button.
b) The Outlet Managed PDU will switch all plugs to the Off state. If all
plugs are already in the Off state, then the unit will reset all plugs to
their user dened default states.