Black Box MPSH8-D20-120V Multi-tool User Manual


 
OUTLET MANAGED PDU
126
Resend Delay: Determines how long the Outlet Managed PDU will wait to
resend an email message generated by this alarm, when the initial attempt to
send the notication was unsuccessful. (Default = 60 Minutes.)
Notify Upon Clear: When this item is enabled, the Outlet Managed PDU
will send additional notication when the situation that caused the alarm has
been corrected. For example, when Notify Upon Clear is enabled, the Outlet
Managed PDU will send initial notication when it detects that a current
consumption has risen above the dened "High" trigger value, and then send
a second notication when it determines that current consumption has fallen
below the "Low" trigger value. (Default = On.)
Email Message: Enables/Disables email notication for this alarm.
(Default = On.)
Note:
The Email Message parameter offers four different options: On, Off,
On (Copy to All Triggers) or Off (Copy to All Triggers). If either of
the "Copy to All Triggers" options is selected, then email notification
for all other alarms will be switched On or Off as indicated by this
parameter. For example, If "Off (Copy to All Triggers)" is selected,
then Email notification will be disabled for all other alarms too.
Address 1, 2, and 3: These parameters are used to select which of the three
email addresses dened via the "Email Messages" menu (see Section 5.9.11)
will receive the email alarm notication messages generated by this alarm.
The Address parameters can be used to select one, or any combination of the
addresses dened via the Email Messages menu. (Default = All On.)
Note:
If Email addresses have been previously specified, then the text
under the parameters will list the current, user defined email
addresses.
Subject: This parameter is used to dene the text that will appear in the
"Subject" eld for all email notication messages generated by this alarm.
(Default = "Alarm: Plug Current")