OUTLET MANAGED PDU
20
Model Numbers
The Outlet Managed PDU series includes a variety of models to accommodate the
power distribution needs of almost any rack mount application.
Model No.
Input
Feeds
Input
Voltage
Max. Load
per Outlet
Max. Load
per Input
Max. Load
per Unit
MPSH8-S20-120V 1 ea, 20 Amp 100 to 120 VAC 12 Amps 16 Amps* 16 Amps*
MPSH8-S20-208+V 1 ea, 20 Amp 100 to 240 VAC 10 Amps 16 Amps* 16 Amps*
MPSH8-D20-120V 2 ea, 20 Amp 100 to 120 VAC 12 Amps 16 Amps* 32 Amps*
MPSH8-D20-208+V 2 ea, 20 Amp 100 to 240 VAC 10 Amps 16 Amps* 32 Amps*
MPSH16-D20-120V 2 ea, 20 Amp 100 to 120 VAC 12 Amps 16 Amps* 32 Amps*
MPSH16-D20-208+V 2 ea, 20 Amp 100 to 240 VAC 10 Amps 16 Amps* 32 Amps*
* In accordance with UL requirements, this value has been de-rated to 80%.