CHAPTER 7: Alarm Configuration
107
Auto Recovery: Enables/Disables the Auto Recovery feature for the selected
branch or line. When both Load Shedding and Auto Recovery are enabled,
the Outlet Managed PDU will return plugs to their former On/Off state after
current load falls below the Alarm Clear Threshold value. This allows the
Outlet Managed PDU to "undo" the effects of Load Shedding after current
load has returned to an acceptable level. (Default = Off.)
Plug Access: Determines which Plug(s) will be switched when current
load exceeds the Alarm Set Threshold and Load Shedding is triggered.
For example, if plugs A1, A2 and A3 are selected, then these plugs will be
switched On or Off whenever current load exceeds the Alarm Set Threshold.
(Default = undened.)
Plug Group Access: Determines which Plug Group(s) will be switched
when the Load Shedding feature is triggered. For example, if you have
dened a Plug Group named "test", which includes Plugs B3, B4 and B5,
and then selected the "test" Plug Group via the Plug Group Access parameter,
then all of the plugs in the "test" Plug Group will be switched On or Off
whenever the current load exceeds the Alarm Set Threshold.
(Default = undened.)
Note:
Plug Groups must first be defined (as described in Section 5.6)
before they will be displayed in the Load Shedding menu’s Plug
Group Access submenu.
After setting parameters for a given branch or line, you may also dene additional
parameters for other branches or lines (if present.) To set Load Shedding parameters
for other branches or lines, return to the Alarm Conguration menu and then repeat
the procedure described in Section 7.1.1.