Black Box MPSH8-D20-120V Multi-tool User Manual


 
OUTLET MANAGED PDU
186
/RB Reboot Options
Displays a menu that is used to congure Scheduled Reboots and Ping-No-Answer
Reboots. Scheduled Reboots allow the Outlet Managed PDU to be rebooted on
a regular basis, according to a user dened schedule. Ping-No-Answer Reboots
allow the Outlet Managed PDU to automatically reboot user-designated outlets
when a user-specied IP address does not respond to a Ping command. For more
information on Reboot options, please refer to Section 6.
Note:
If desired, the Ping-No-Answer Reboot function can also be
configured to send email notification whenever a Ping-No-Answer
Reboot is generated. For more information, please refer to
Section 7.5.
Availability: Administrator
Format: /RB [Enter]
/AC Alarm Configuration Parameters
Displays a menu that is used to congure and enable the Over Current Alarms, Over
Temperature Alarms, Circuit Breaker Open Alarm, Lost Voltage Alarm, Ping-No-
Answer Alarm, Invalid Access Lockout Alarm and Plug Current Alarm. When
properly congured, the Over Current Alarms and Over Temperature Alarms offer
the option of "Load Shedding", which allows the unit to automatically switch Off
user-specied non-essential outlets when temperature or current readings exceed
user-dened values. For more information on Alarm Conguration, please refer to
Section 7.
Availability: Administrator
Format: /AC [Enter]