The Load Shedding Conguration Menus allow you to dene the following
parameters:
Notes:
• In the Web Browser Interface, the "Unit to Configure" and "Branch"
parameters are found in the Over Current Alarm configuration
menus.
• The "Unit to Configure," "Branch A," "Branch B" and "Line"
parameters are used to determine which unit or branch the Load
Shedding functions will be applied to.
• The Line Alarms are not available on some Outlet Managed PDU
models.
Unit to Congure: In some compatible power control products, this item is
used to select either a local unit or an auxiliary unit. In Outlet Managed PDU
series products, this option has no function. (Default = Local.)
Branch A Load Shedding: Denes the Load Shedding actions that will be
executed when an Over Current Branch Alarm is triggered at Branch "A".
Branch B Load Shedding: Denes the Load Shedding actions that will be
executed when an Over Current Branch Alarm is triggered at Branch "B".
Line Load Shedding: Denes the Load Shedding actions that will be
executed when an Over Current Line Alarm is triggered (not available on
some Outlet Managed PDU models.)
After selecting the branch or line, use the following parameters to congure Load
Shedding functions for the desired branch or line.
Enable: Enables/Disables Load Shedding for the corresponding alarm.
When enabled, the Outlet Managed PDU will switch the user specied plugs
whenever current load exceeds the Alarm Set Threshold value.
(Default = Disable.)
Plug State: Determines whether the selected plugs/plug groups will be
switched On or Off when Load Shedding is enabled and current load exceeds
the user-dened Alarm Set Threshold. For example, if the Plug State is
"Off", then plugs or plug groups will be switched Off when the Alarm Set
Threshold is exceeded. (Default = Off.)