OUTLET MANAGED PDU
120
To congure the Invalid Access Lockout Alarm, you must access the Outlet Managed
PDU command mode using a password that permits Administrator Level commands.
The Invalid Access Lockout alarm conguration menu offers the following
parameters:
• Trigger Enable: Enables/Disables the trigger for this alarm. When
Disabled, this alarm will be suppressed. (Default = On.)
Note:
To cancel an alarm without unlocking the port, simply toggle the
Trigger Enable parameter Off and then back On again.
• Resend Delay: Determines how long the Outlet Managed PDU will wait to
resend an email message generated by this alarm, when the initial attempt to
send the notication was unsuccessful. (Default = 60 Minutes.)
• Notify Upon Clear: When this item is enabled, the Outlet Managed PDU
will send additional notication when the situation that caused the alarm has
been corrected. For example, when Notify Upon Clear is enabled, the Outlet
Managed PDU will send initial notication when it detects that an Invalid
Access Lockout has occurred, and then send a second notication when it
determines that the port has been unlocked. (Default = On.)
• Email Message: Enables/Disables email notication for this alarm.
(Default = On.)
Note:
The Email Message parameter offers four different options: On, Off,
On (Copy to All Triggers) or Off (Copy to All Triggers). If either of
the "Copy to All Triggers" options is selected, then email notification
for all other alarms will be switched On or Off as indicated by this
parameter. For example, If "Off (Copy to All Triggers)" is selected,
then Email notification will be disabled for all other alarms too.