Black Box MPSH8-D20-120V Multi-tool User Manual


 
OUTLET MANAGED PDU
158
13.5. Viewing Outlet Managed PDU Status via SNMP
Status of various components of the Outlet Managed PDU can be retrieved via
SNMP. Plug Status, and Environmental Status are currently supported.
13.5.1. Plug Status
The status of each plug in the system can be retrieved using the command below.
plugTable::plugStatus – The status of the plug.
0 – Plug is OFF
1 – Plug is ON
plugTable::plugName - String indicating the plug’s user-dened name.
13.5.2. Unit Environment Status
The environment status can be retrieved for various variables for all of the Outlet
Managed PDUs in the system. The environmentUnitTable contains four rows, one
row for each unit in the system (LOCAL, AUX1, AUX2, AUX3.)
environmentUnitTable::environmentUnitName – The unit
(LOCAL.)
environmentUnitTable::environmentUnitTemperature
The temperature of the given unit.
environmentUnitTable::environmentUnitCurrentA – Unit’s
total current for Branch A. Note that Current will be reported in tenths of an
Amp (divide result by ten to determine value in Amps.)
environmentUnitTable::environmentUnitVoltageA – Unit
voltage for Branch A
environmentUnitTable::environmentUnitPowerA – Power
drawn by Branch A
environmentUnitTable::environmentUnitCurrentB – Unit’s
total current for Branch B. Note that Current will be reported in tenths of
an Amp.
environmentUnitTable::environmentUnitVoltageB – Unit
voltage for Branch B
environmentUnitTable::environmentUnitPowerB – Power
drawn on Branch B
environmentMonthlyPowerLog - The monthly power usage log.