Black Box MPSH8-D20-120V Multi-tool User Manual


 
OUTLET MANAGED PDU
22
7. Branch A Current Usage: A bank of ten LEDs which light to indicate total
current usage on Power Circuit A. The rst LED will light when 0% to 9%
of maximum rated current for the power circuit is being used, and the last
LED will blink when over 100% of the maximum rated current for the power
circuit is being used.
8. Branch B Current Usage: Same as Item 7 above, except displays values for
Power Circuit B. (Not present on MPSH8-S20-120V and
MPSH8-S20-208+V models.)
3.2. Outlet Managed PDU-H Series - Back Panel
As shown in Figure 3.2, the Outlet Managed PDU Back Panel includes the following
components:
1. Power Circuit A - Power Inlet: An IEC320-C20 AC inlet which supplies
power to Outlet Managed PDU control functions and the Circuit "A" outlets.
Also includes cable keeper (not shown.)
Note:
MPSH8-S20-120V and MPSH8-S20-208+V models feature a single
Power Inlet.
2. Power Circuit B - Power Inlet: An IEC320-C20 AC inlet which supplies
power to Outlet Managed PDU control functions and the Circuit "B" outlets.
Also includes cable keeper (not shown.) (Not present on MPSH8-S20-120V
and MPSH8-S20-208+V models.)
3. Power Circuit A - Switched Outlets: AC Outlets that can be switched On,
Off, rebooted or set to default state in response to user commands.
4. Power Circuit B - Switched Outlets: Same as Item 3 above. (Not present
on MPSH8-S20-120V and MPSH8-S20-208+V models.)
5. Alarm Indicator Lights: Two LEDs which light when an alarm condition
is detected at the corresponding power circuit. Note that MPSH8-S20-120V
and MPSH8-S20-208+V models only include one power circuit and one
Alarm Indicator Light. For information on Alarm Conguration, please refer
to Section 7.