Q Table of output terminal functions 2
Function
No.
Code Function Action
12 OT Over-torque detection ON: Torque current is equal to or larger than
H set value and longer than H
set time.
OFF: The torque current is equal to or less than
(H set value - H set value).
13 OTN Inversion of over-torque detection Inversion of OT
14 RUN Start/Stop ON: When operation frequency is output or during
(FD)
OFF: Operation stopped
15 RUNN Inversion of RUN/STOP Inversion of RUN setting
16 POL OL pre-alarm ON: 50% or more of calculated value of overload
protection level
OFF: Less than 50% of calculated value of
overload protection level
17 POLN Inversion of OL pre-alarm Inversion of POL setting
18 POHR Braking resistor overload pre-alarm ON: 50% or more of calculated value of H
set overload protection level
OFF: Less than 50% of calculated value of
H set overload protection level
19 POHRN Inversion of braking resistor overload pre-alarm Inversion of RCHR setting
20 POT Over-torque detection pre-alarm ON: Torque current is equal to or larger than 70%
of H set value.
OFF: The torque current is below (H set
value x 70% - H set value).
21 POTN Inversion of over-torque detection pre-alarm Inversion of POT setting
22 PAL Pre-alarm One of the following is turned on:
ON POL, POHR, POT, MOFF, UC, OT, LL
stop, COT, and momentary power failure
slowdown stop.
or E,R,QTJ issues an alarm
All the following are turned off:
OFF POL, POHR, POT, MOFF, UC, OT, LL
stop, COT, and momentary power failure
slowdown stop.
or E,R,QTJ issues no alarm
23 PALN Inversion of pre-alarm Inversion of PAL setting
24 UC Small-current detection ON: The output current is equal to or less than
H set value for H set time.
OFF: The output current is equal to or larger than
H set value + 10%.
25 UCN Inversion of small-current detection Inversion of UC setting
26 HFL Significant failure ON: QEC,QEN,QV,G,
GGR,GVP,GRJQ,GTT-
,QJ,WR,GH,WE,
GV[R,QTGRJ)
OFF: Failure other than the above
27 HFLN Inversion of significant failure Inversion of HFL setting
28 LFL Insignificant failure ON: (QE-,QR-,QJ,
QN-,QNT)
OFF: Failure other than the above
29 LFLN Inversion of insignificant failure Inversion of LFL setting
30 RDY1 Ready for operation (including ST/RUN) ON: Ready for operation (ST and RUN are also
ON)
OFF: Others
31 RDY1N Inversion of ready for operation (including
ST/RUN)
Inversion of RDY1 setting
32 RDY2 Ready for operation (excluding ST/RUN) ON: Ready for operation (ST and RUN are not
ON)
OFF: Others
33 RDY2N Inversion of ready for operation (excluding ST/RUN) Inversion of RDY2
34 FCVIB Frequency VIB selection ON: VIB selected as frequency command
OFF: Terminal other than VIB selected as
frequency command